4.2 Commissioning
The room thermostats are delivered with a fixed set of applications.
Select and activate the required application during commissioning using one of
the following tools:
– Local DIP switch and HMI
– Synco ACS
– ETS
(Parameter and application download with ETS will be implemented later)
Set the DIP switches before snapping the thermostat to the mounting plate, if
you want to select an application via
DIP switches
.
All DIP switches need to be set to OFF (remote configuration), if you want to
select an application via
commissioning tool
.
After power is applied, the thermostat resets and all LCD segments blink, indica-
ting that the reset was correct. After the reset, which takes about 3 seconds, the
thermostat is ready for commissioning by qualified HVAC staff.
If all DIP switches are set to OFF, the display reads
NO APPL
to indicate that
application commissioning via tool is required.
Each time the application is changed, the thermostat reloads the factory setting
for all control parameters, except for KNX device and zone addresses!
Connect the Synco ACS or ETS tool to the KNX bus cable at any point for
commissioning:
ACS and ETS require an interface:
– RS232 KNX interface (e.g. SiemensUP146/02, UP152)
– OCI702 USB-KNX interface
An external KNX bus power supply is required if an RDG.. is connected directly
to a tool (ACS or ETS) via KNX interface.
Applications
DIP switches
NO APPL
Note
Connect tool
Note