73 / 87
Siemens
RDG400KN,RGD405KN Basic documentation
CE1P3192en
Building Technologies
2017-02-17
4.3 Operation
See also Operating Instructions B3192 [2] enclosed with the thermostat.
1.
Operating mode selector/Esc
2.
Protection and OK
3.
Rotary knob to adjust setpoints
and parameters
User action
Effect, description
Normal operation
Actual operating mode and state are
indicated by symbols.
Press any button
(thermostat in normal operation)
Enter operating mode selection;
backlit LCD turns on, all possible mode
symbols turn on, indicator element (arrow)
appears on the current mode/state.
Press left button
Change operating mode (indicator element
(arrow) changes to the next mode symbol.
After the last press and a timeout of 3
seconds, the newly selected mode is
confirmed, the other elements disappear.
After a timeout of 20 seconds, the LCD
backlight turns off.
Press left button (P01 = 2)
Toggle between heating and cooling.
Press left button while "Operating
mode" via bus is Economy or while
operating mode switchover contact is
activated
Activate "Extend Comfort mode"
(for details, see page 20).
Keep left button depressed and
turn rotary knob clockwise/counter-
clockwise
Activate timer "Extend presence"/"Extend
absence" and set the time (for details, see
page 20).
Press right button >3 seconds
Activate/deactivate button lock.
Press right button
Set thermostat to Protection mode or back
to the previous operation mode.
Turn rotary knob
Adjust the room temperature Comfort
setpoint.
Hold down both the left and right
buttons simultaneously for 4 seconds.
Release them, and hold the right
button again within 2 seconds until
the temperature disappears
Enter parameter setting mode Service level.
Hold down both the left and right
buttons simultaneously for 4 seconds.
Release them, and hold the left
button again within 2 seconds until
the temperature disappears. Turn the
rotary knob counterclockwise
minimum ½ rotation.
Pxx
displays.
Continue with step 2
Enter parameter setting mode "Expert level,
diagnostics and test".
Press left and right button simultane-
ously for 6 seconds
Enter (KNX) programming mode.
Layout
Button operation
2
1
3