75 / 87
Siemens
RDG400KN,RGD405KN Basic documentation
CE1P3192en
Building Technologies
2017-02-17
4.4 Remote
operation
The RDG.. room thermostats can be operated from a remote location using an
OZW772/OZW775 web server or the ACS tool.
4.5 Disposal
In terms of disposal, the room thermostats are classified as electronic scrap
conforming to the European Directive 2012/19/EU and must not be disposed of
as domestic waste.
∂
Dispose of the device via the channels provided for this purpose
∂
Comply with all local and currently applicable laws and regulations
5. Supported KNX tools
5.1 ETS
ETS is an engineering tool used to fully commission the RDG4..KNX room
thermostats.
ETS can implement the following functions:
– Defining and downloading the physical address
– Defining and downloading the application (plant type, control sequence)
– Setting up and downloading the thermostat's control parameters
– Setting up and downloading group addresses
This Basic Documentation does not describe how to operate the ETS tool and
commission a device. Refer to the KNX Manual for more details.
Setting RDG..KNX parameters is only supported by ETS4 or higher!
To start KNX programming, press left and right button simultaneously for at least
6 seconds.
5.1.1 Parameter settings in ETS
1. Open the project in ETS and select a device.
2. Click
Parameters
tab, and adjust the control parameters as follows:
3. The
Plant type
(application),
Control Sequence
and other control
parameters ([Pxx] description) can be downloaded.
ETS
STOP
Note
Addressing mode