A6V101035988_en--_d 2018-06-21
Subject to alteration
Siemens Building Technologies / HVAC Products
Parameter setting
Parameter setting mode
1. Press LEARN on the rear for 5 seconds until “P01” appears.
2. Press LEARN again and the parameter value on second line flashes
and is ready for adjustment.
3. Adjust the parameter using setting knob.
4. Press LEARN once to confirm the setting.
5. Rotate the setting knob clockwise to next parameter and repeat steps 2
to 4.
6. Exit parameter setting mode by rotating the setting knob clockwise to
“End” and pressing LEARN button once.
Parameters:
·
P01
Control behaviour
:
2-position 1K / 2-position 0.5 K / PID fast / PID
slow (factory-setting)
·
P02
Maximum temperature range
·
P03
Minimum temperature range
Front View Receiver
LED Signal Indicator
LED Relay Indicator
The signal is good when the
LED flashes green.
A flashing red LED indicates
that there is no signal.
Orange LED indicates relay is on.
OVERRIDE Button
Press this button to overwrite transmitter
values.
RESET: Press the LEARN & OVERRIDE
button for 4 seconds to delete all transmitter
addresses.
LEARN Button
Rear View Room
Unit
(Transmitter)
Press the button to learn a transmitter
address.
Learn Button
TEST Button
Press and then release to
learn telegram
Used for testing transmission.
Press > 5 s to enter
parameter mode
NOTE:
You can press the OVERRIDE button on the receiver to manually switch ON/OFF for a faulty room unit
or transmission protocol.
NOTE:
You must re-execute the workflow for commissioning the set to reestablish a connection between the
room controller and receiver.
Configuration instructions for the Siemens RDH100RF/SET
The transmitter RDH100RF and the receiver RCR100/433 are set to communicate (bonded) with each
other at the factory. If they fail it is necessary to re-bond the units due to the loss of communication,
please follow the below instructions.
1. Reset receiver by simultaneously pressing the LEARN & OVERRIDE button for 4 seconds.
2. Press and release the LEARN button. This sets the receiver to the learn mode.
3. Press and release the LEARN button on the back of the transmitter.
4. A green flashing or solid LED indicates a good signal, a red flashing or solid LED indicates no
signal.
5. To test transmission, press the TEST button on the transmitter, switches the relay on in
the receiver regardless of temperature. The RF TEST symbol appears on the thermostat display.
6. An orange LED indicates that the relay is on.
DE
EN
FR
IT
NL
ES
PT
CS
HU
PL
SV
FI
ZH
TR
EL
RO
DA