21 / 32
Siemens
RDU340… Basic Documentation
CE1P3078en
Building Technologies
Functions
2014-11-03
#
Parameter
Factory
setting
Setting range
R
D
U
3
4
0
Service Level
P01 Control
sequence
(for application "single duct" only)
1 (Cooling only)
0:= Heating only
1:= Cooling only
2:= Manual H/C
3:= Auto changeover
ü
P02
Mode selection via user operating mode button
1 (Stb, Comf)
1 = Stb,Comf
2 = Stb, Comf, Eco
ü
P04
Selection of °C or °F
°C
(0) °C
(1) °F
ü
P05 Sensor
calibration
0.0 K
– 3 ... +3 K
ü
P06
Standard
temperature
display
0 (Room temp)
0:= Room temperature
1:= Setpoint
ü
P07
Additional
user
info
0 (no display)
0:= no display
1:= Temp in °C and °F
ü
P08
Comfort
basic
setpoint
21 °C
5 ... 40 °C
ü
P09
Minimum setpoint limitation for Comfort (WminComf)
5 °C
5 ... 40 °C
ü
P10
Maximum setpoint limitation for Comfort (WmaxComf)
35 °C
5 ... 40 °C
ü
P11
Heating setpoint for Energy Saving (WheatEco)
15 °C
OFF, 5 °C…WcoolEco
ü
P12
Cooling
setpoint
for Energy
Saving (WcoolEco)
30 °C
OFF, WheatEco…40 °C
ü
P14 Key
lock
(Press the operating mode button
for 7 seconds to
enable or disable the key lock)
0 (Unlocked)
0:= Unlocked
1:= Auto lock
2:= Manual lock
ü
·
P01 is not available when the controller is commissioned as single duct with el.
heater (DIP switch #1 = ON)
·
P02 is not available when the controller is commissioned for manual
heating/cooling changeover (P01=2)
·
Parameter display depends on selected application and function
(x) Not available
Control parameters
Note