22 / 32
Siemens
RDU340… Basic Documentation
CE1P3078en
Building Technologies
Functions
2014-11-03
#
Parameter
Factory
setting
Setting range
R
D
U
3
4
0
Expert Level
P30
P-band/switching differential for heating mode
2K
0.5 … 6 K
ü
P31
P-band/switching differential for cooling mode
1 K
0.5 … 6 K
ü
P33
Dead zone in Comfort mode
2 K
0.5 … 5 K
ü
P35
Integral time
5 min
0…10 min
ü
P36
Heating/cooling changeover switching point for cooling
16 °C
10…25 °C
ü
P37
Heating/cooling changeover switching point for heating
28 °C
27…40 °C
ü
P38
X1 functionality
3 (Op mode
switchover)
0:= NA
1:= Ext/Return air temp
2:= Heat/cool changeover
3:= Operating mode switch
4:= Dewpoint monitor
5:= Enable electrical heater
6:= Alarm input
ü
P39
Operating action for X1 if digital input
0 (N.O.)
0:= Normally open
1:= Normally closed
ü
P40
X2 functionality
2 (H/C c/o) Same as P38
ü
P41
Operating action for X2 if digital input
0 (N.O.)
0:= Normally open
1:= Normally closed
ü
P51
Flow temp limit floor heating
OFF
OFF, 10...50 °C
ü
P58
“no function”
ON
ü
P63
Minimum output limitation air flow signal (0..10V)
0%
0…100%
ü
P64
Maximum output limitation air flow signal (0..10V)
100%
0…100%
ü
P65
Heating setpoint for Standby
(Wheat
Stb
)
8 °C
OFF, 5 °C…Wcool
Stb
ü
P66
Cooling setpoint for Standby
(Wcool
Stb
)
OFF
OFF, Wheat
Stb
…40 °C
ü
P69
Temporary setpoint for Comfort mode
OFF
OFF:= Disabled
ON := Enable
ü
P71
Parameter reset
Set value to ON and confirm by pressing the
+
and
–
buttons
OFF
OFF:= Idle
ON: = Reset
ü
Diagnostic & Test
d01
Application
Diagnose
2P:=
single
duct
2PEL:=
single duct & el. heater
ü
d02
Status input X1
Diagnose
0:= Digital input not activated
1:= Digital input activated
0…49 °C = measured temp. value
00 := H/C input short
100:= H/C input open
ü
d03
Status input X2
Diagnose
Same as d02
ü