28 / 32
Siemens
RDU340… Basic Documentation
CE1P3078en
Building Technologies
Technical data
2014-11-03
8 Technical
data
Operating voltage
SELV AC 24 V
±
20 %
or
AC 24 V class 2 (UL)
Frequency
50/60 Hz
Power consumption
Max. 8 VA
External supply line protection (EU)
Circuit breaker max. 10 A
Characteristic B, C, D
according to EN 60898
or
Power source with current
limitation of max. 10 A
No internal fuse
External preliminary protection with max. C 10 A circuit breaker
required in all cases
Control output Y10-G0
Resolution
Current
SELV DC 0…10 V
39 mV
Max.
±
1 mA
Control output Y21-L (N.O.)
Rating
AC 230 V
5 mA…5(2) A
No internal fuse
External preliminary protection with max. C 10 A circuit breaker in the supply line
required under all circumstances
Multifunctional input X1-M/X2-M
Temperature sensor input: Type
Digital input:
Operating
action
Contact sensing
Insulation against mains voltage (SELV)
NTC (3 k
W
at 25 °C)
Selectable (N.O./N.C.)
SELV DC 0...5 V/max 5 mA
4 kV, reinforced insulation
Function input:
External temperature sensor, heating/cooling changeover
sensor, operating mode switchover contact, dewpoint
monitor contact, enable electrical heater contact, alarm
contact
Selectable
Switching differential, adjustable
Heating mode
(P30)
Cooling mode
(P31)
2 K (0.5...6K)
1 K (0.5...6K)
Setpoint setting and range
Comfort mode
(P08)
Energy Saving mode
(P11-P12)
Standby
(P65-P66)
21°C (5...40 °C)
15°C/30°C (OFF, 5...40 °C)
8°C/OFF (OFF, 5...40 °C)
Multifunctional input X1/X2
Input X1
Input
X2
Selectable 0…6
3: (P38) operating mode
switchover
2: (P40) heating/cooling
changeover sensor
Multifunctional input X1/X2
Selectable 0…6
Input X1
Factory setting = 3 (P38)
Input
X2
Factory setting = 2 (P40)
Operating mode switchover
Heat/cool changeover sensor
Power supply
Warning
Outputs
Warning
Inputs
Operational data