3.4 Applications
overview
The thermostats support the following applications, which can be configured using
the DIP switches inside the front panel of the unit or a commissioning tool.
All DIP switches need to be set to OFF (remote configuration, factory setting) to
select an application via commissioning tool. In this case the output signal type
needs to be set in ACS as well.
The tool offers the applications printed in bold text (basic applications).
Application and output signal
Diagram
DIP switches
Remote configuration
via commissioning tool (factory setting)
·
Synco ACS
·
ETS
1
ON
2
3
Single duct
·
Single duct heating or cooling
DC 0...10 V output signal normal
3
1
9
2
S
0
7
B1
T
M
V
M
V
YV
1
ON
2
3
·
Single duct heating or cooling
DC 10...0 V output signal inverted
1
ON
2
3
Single duct with electric heater
·
Single duct heating and cooling, with
electric heater
DC 0...10 V output signal normal
3
1
9
2
S
0
8
YE
B1
T
M
V
M
V
YV
1
ON
2
3
·
Single duct heating and cooling, with
electric heater
DC 10...0 V output signal inverted
1
ON
2
3