29 / 68
Siemens
RDU341 Basic Documentation
CE1P3172en
Building Technologies
2015-06-08
3.6.4 Single-duct
On single-duct applications, the thermostat controls an actuator (air damper, VAV
system, valve etc.)…
– in heating / cooling mode with changeover (automatic or manual),
– heating only mode,
– or cooling only mode.
Cooling only is factory-set (P01=1).
The output signal for the air flow can be limited to a minimum and maximum value
if required (see section 3.5).
Modulating control: DC 0…10 V
The diagrams below show the control sequence for modulating PI control.
Heating only (P01 = 0)
Cooling only (P01 = 1)
Changeover (P01 = 2, 3)
T[°C] Room
temperature
XpH Proportional band
“Heating”
w
Room temperature setpoint
XpC Proportional band
“Cooling”
Y
Control command “Actuator”
Vmin Min. limitation for output
Vmax Max. limitation for output
The diagrams show the PI controller’s proportional part only.
Setting the sequence and the control outputs
Refer to section 3.4, section 3.6.1, and section 3.7.
Note: