3.6.6 Setpoints and sequences
·
Comfort setpoint (W) is in the currently active heating or cooling sequence
·
Comfort setpoint (W) is in the heating sequence
·
If the supply air temperature is available (via KNX), the air
flow may also increase when the room temperature is
below the heating setpoint
·
If no supply air temperature is available, sequence for air
flow control is Cooling only
The setpoints for Economy and Protection mode are below the Comfort setpoints
(heating) and above the Comfort setpoints (cooling).
They can be set via parameters P11, P12 (Economy mode) and P65, P66
(Protection mode). .
Comfort mode
Economy / Protection mode
Application
Heating
Cooling
Heating
Cooling
Single duct
Heating and Cooling
Heating and Cooling
Single duct with
el. heate
W = setpoint in Comfort mode
W
HeatEco/Prot
= setpoint heating in Economy or Protection mode
W
CoolEco/Prot
= setpoint cooling in Economy or Protection mode
Y = air / water sequence
T = room temperature
The dead zone can be adjusted via parameter P33.
Single duct / single
duct with heating /
cooling coil
Single duct with el.
heater / radiator / floor
heating
Changeover air
Economy, Protection
Y