49 / 68
Siemens
RDU341 Basic Documentation
CE1P3172en
Building Technologies
2015-06-08
3.12.3 Parameters of the "Service level"
P
a
ra
m
e
te
r
Name
Factory setting
Range
Service level
P01 Control
sequence
1
0 = Heating only
1 = Cooling only
2 = H/C changeover manual
3 = H/C changeover auto
P02
Operation via room op selector
1
1 = Auto - Protection
2 = Auto - Comfort - Economy -
Protection
P04 Unit
0
0 = °C
1 = °F
P05
Measured
value
correction
0 K
– 3 ... 3 K
P06 Standard
display
0
0 = Room temperature
1 = Setpoint
P07
Additional
display
information
0
0 = --- (No display)
1 = °C and °F
2 = Outside temperature (via bus)
3 = Time of day (12h) (via bus)
4 = Time of day (24h) (via bus)
P08
Comfort
basic
setpoint
21 °C
5 ... 40 °C
P09
Comfort
setpoint
minimum
5 °C
5 ... 40 °C
P10
Comfort
setpoint
maximum
35 °C
5 ... 40 °C
P11
Economy
heating
setpoint
15 °C
OFF, 5 ... WCoolEco;
WCoolEco = 40 °C max
P12
Economy
cooling
setpoint
30 °C
OFF, WHeatEco ... 40 °C;
WHeatEco = 5C min
P14 Button
lock
0
0 = Unlocked
1 = Auto lock
2 = Manual lock
Parameter display depends on selected application and function.
Note: