4.2 Commissioning
The room thermostats are delivered with a fixed set of applications.
Select and activate the relevant application during commissioning using one of the
following tools:
– Local DIP switch and HMI
– Synco ACS
– ETS
Set the DIP switches before snapping the front panel to the mounting plate, if you
want to select an application via
DIP switches
.
All DIP switches need to be set to “OFF” (remote configuration), if you want to
select an application via
commissioning tool
.
After power is applied, the thermostat resets and all LCD segments flash, indicating
that the reset was correct. After the reset, which takes about 3 seconds, the
thermostat is ready for commissioning by qualified HVAC staff.
If all DIP switches are OFF, the display reads "NONE" to indicate that application
commissioning via a tool is required.
Each time the application is changed, the thermostat reloads the factory setting for
all control parameters, except for KNX device and zone addresses!
Connect the Synco ACS or ETS tools to the KNX bus cable at any point for
commissioning:
N1
3
1
7
2
A
0
4
..
KNX
ETS
RS232
Siemens
N148
UP146
UP152
ETS/ACS
Siemens
OCI700
OCI702
G
G0
Y21
Y10
G0
X1
M
X2
L
CE+ CE-
ACS and ETS require an interface:
– RS232 KNX interface (e.g. Siemens N148 / UP146 / UP152)
– OCI700, OCI702 interface
An external KNX bus power supply is required if an RDU is connected directly to a
tool (ACS or ETS) via KNX interface.