The thermostat's control parameters can be set to ensure optimum performance of
the entire system.
The parameters can be adjusted using
– Local HMI
– Synco ACS
– ETS
The control parameters of the thermostat can be set to ensure optimum
performance of the entire system (see section 3.12).
·
The control sequence may need to be set via parameter P01 depending on the
application. The factory setting is as follows:
Application
Factory setting P01
Single duct
1 = cooling only
Single duct with el. heater
Not adjustable
·
Recalibrate the temperature sensor if the room temperature displayed on the
thermostat does not match the room temperature measured (after min. 1 hour of
operation). To do this, change parameter P05
·
We recommend to review the setpoints and setpoint ranges (parameters
P08…P12) and change them as needed to achieve maximum comfort and save
energy
The programming mode helps identify the thermostat in the KNX network during
commissioning.
Press buttons “operating mode”
and “+” simultaneously for 6 sec to activate
programming mode, which is indicated on the display with "PrOg".
Programming mode remains active until thermostat identification is complete.
Use ETS to assign the KNX group addresses of the thermostat's communication
objects.
Each device has a unique KNX serial number inside the front panel.
An additional sticker with the same KNX serial number is enclosed in the
packaging box. This sticker is intended for installers for documentation purposes.
Control parameters
Control sequence
Calibrate sensor
Setpoint and range
limitation
Programming mode
Assign KNX group
addresses
KNX serial number