CE1B3074en / 28.07.2003
Subject to alteration
Siemens Building Technologies / HVAC Products
Commissioning (by qualified HVAC staff)
Parameter
Setting range
Factory setting
User setting
(Please record all
changes you make)
P01
Setpoint of heating in energy saving mode
(operating mode changeover switch activated)
OFF, 8…18
°
C in increments of 0,5 K
16 °C
P02
Setpoint of cooling in energy saving mode
(operating mode changeover switch activated)
OFF, 24…35
°
C in increments of 0,5 K
28 °C
P03
Minimum setpoint limitation in normal mode
8… 20 °C in increments of 1 K
8 °C
P04
Maximum setpoint limitation in normal mode
21…35 °C in increments of 1 K
35 °C
P05
Minimum compressor off-time, outputs Y14, Y24 (heat pump)
1...10 Minutes (in increments of 1 Min.)
3 Min.
P06
Minimum compressor on-time, outputs Y14, Y24 (heat pump)
1...10 Minutes (in increments of 1 Min.)
1 Min.
P07
Auxiliary heater minimum hold time
1...10 Minutes (in increments of 1 Min.)
1 Min.
P08
Fan overrun after auxiliary heater shut down
30...300 Seconds (in increments of 10 Sec.)
30 Sec.
P09
Sensor calibration
-3…+3 K in increments of 0,5 K
0 K
P10
P-band in heating mode
0.5…+4 K in increments of 0,5 K
2 K
P11
P-band in cooling mode
0.5…+4 K in increments of 0,5 K
1 K
P12
Setpoint differential between heating and auxiliary heating
0.5…+5 K in increments of 0,5 K
2 K
P13
Value of current room temperature (only display, no setting)
0…49 °C
-
P14
Active temperature sensor (only display, no setting)
1: Room temperature sensor active
2: Remote temperature sensor active
-
Changing the control parameters
To optimize the control performance, a number of control parameters can be adjusted. This can also be
made during operation without opening the controller.
Do you want to change the control parameters of the heating and / or cooling setpoints in the normal or
energy saving mode? Or do you want to increase / decrease the switching differential in heating and
cooling mode?
Then, proceed as follows:
(For factory settings, see above under “Commissioning)
Sensor calibration
If the room temperature displayed by the controller does not match with the temperature effectively
measured, the temperature sensor can be recalibrated. For that purpose, parameter P09 must be
changed
Proceed as described under “Changing the control parameters” and follow steps 1 through 3 to
select parameter P09.
With step 4, the room temperature displayed can now be matched to the temperature
effectively measured. Each push of the + or – button changes the temperature by + or – 0.5 °C
up to a maximum of + / - 3 °C. With step 7, the recalibration is automatically stored 10 seconds
after the last readjustment..
DIP-switch setting
DIP-
switch
Function
Position ON
(Factory setting)
Position OFF
1
Operating action of
remote ON/OFF switch
Changeover activated when
switch is closed (N.O.)
Changeover activated
when switch is open (N.C.)
2
Auxiliary heat function
No auxiliary heater connected
Auxiliary heater connected
3
Display of
temperature/setpoint
Room temperature
Temperature setpoint
1. Normal operation mode
/
2. Press the + and – buttons simultaneously for a min. of 3 and a max. of 5 seconds.
Release them and within 2 seconds, press the + button again for 3 seconds. The
display will show “P01”.
3. Select the required parameter by repeatedly pressing the + or – button:
4. Press the + and – buttons simultaneously, the current value of the selected
parameter appears, which can be changed by repeatedly pressing the + or –
button.
5. By pressing b and - simultaneously again or 5 seconds after the last press
of a button, the last parameter will be displayed again.
6. If you wish to display and change additional parameters, repeat steps 3 through 5.
7. 10 seconds after the last display or setting, all changes will be stored.