RDX33… / RDX43...

RDX33… / RDX43... – the temperature controller that allows you to set the ideal room temperature you want. The controller provides 
protection-,comfort-, energy saving- or auto timer mode with 8 programmable timers.  

1.5V

'AA'

1.5V

'AA'

+

-

Operation

Warmer / colder

setting the

temperature setpoints

and the time of day

3075Z01en

Display

Button operating mode

Settings

Heating / cooling 

changeover button

 

°C 

  Temperature 

°F 

  Temperature 

1...7

 

   

Weekday

 
Commissioning

 

Initial  
power-up 

  Remove the black transit tabs from the 2 alkaline batteries. Check to see if the battery holder is in its correct position. If no 

  batteries are inserted, fit 2 alkaline batteries type AA in the battery compartment 

  Once batteries are fitted, all symbols will appear on the display as shown for about 2 seconds. 

Setting the time of day and the weekday 

 

   

 

   

 

1. Keep the 

 button pressed until the time digits start to flash and then press 

 or 

 to set the time of day. If the current 

  time is the 24-hour format and you wish to change to the 12-hour format, set P17 to 0 = 12-hour format (or vice versa 1 back 
  to the 24-hour format). 
2. Confirm the time of day by pressing 

 and the weekday indicator starts to flash. 

3. Press 

 or

 to set the current weekday. 

4. Confirm the current weekday by pressing 

 

Are your rooms too warm or too cold? 

Do you want to set your controller to protection? 

 

 

 
 
 

 

 

Press the 

 

 

 

 button several times until the display shows the 

 symbol 

to indicate that protection is selected. 
 

In protection 

, the controller maintains the adjusted lower setpoint of heating 

(parameter P03) or the higher setpoint of cooling (parameter P04).  

Important:

 

If the setpoint of protection is set to 

OFF 

(factory setting)

the controller will not be 

active. 

Risk of frost!

 

Do you want to change from heating to cooling mode? 

 

 

 / 

 

 

The changeover between cooling and heating is done by a remote changeover 
switch.  
 
When pressing the 

 button, the controller changes from heating to cooling or vice 

versa.

 

Do you want to change to auto timer-, comfort or energy saving mode? 

 

 /   

 

Press the 

 

 

 

 button several times until the display shows the symbols to 

indicate which mode you want to select. 
 
The controller will automatically change over comfort mode and energy saving mode 
according to the 8 preprogrammed timers. 

Do you want to set the programmable timer settings? 

 

A..

   

 

 

A..

     

 

A..   

1

 

 

To adjust the time schedule, keep the 

 button pressed for 3 seconds to go to 

the programmable timer setting mode.  
This mode is indicated by displaying Ax (x= auto timer 1...8) and the time xx:xx 
flashing. For each auto timer, proceed as follows: 

1. The  and 

 symbols are displayed. Press 

 or 

 to adjust the comfort 

operation start time and confirm by pressing 

2. The  and   symbols are displayed. Press 

 or 

 to adjust the comfort 

operation end time or energy saving start time respectively and confirm by 
pressing 

3. Symbol 

1

 will flash. Press 

 or 

 to select or deselect each day and 

advance to the next day. Confirm setting for actual timer by pressing 

 

and advance to the next timer 

The controller will leave the programmable timer setting mode if no button is pressed 
within 20 seconds. All changes made after the last press of 

 button will not be 

saved.

 

 

   

Only applicable in comfort operation. 
Pressing 

 or 

 allows you to increase or decrease the current room temperature 

setpoint for comfort operation in increments of 0.5 °C. The maximum setting range is 
from 5...40 °C, unless it is limited by parameters P05 and P06.

 