4/8

Siemens Building Technologies

Room temperature controller REV100

CE1N2211en

Landis & Staefa Division

16.05.2000

Select the economy temperature 

 and press the time button, then enter the num-

ber of days you are absent 

 (max. 99 days). The display will show the num-

ber of days and the holiday symbol. Every midnight, the counter subtracts one day.

When the day counter reaches 00, the 24-hour operation with two heating phases will
automatically be resumed.

Press the day counter and set it to 00.

If the temperature displayed does not agree with the room temperature effectively
measured, the temperature sensor can be re-calibrated. For that purpose, set the DIP
switch for Sensor Alignment to ON and press the DIP switch button.

Press 

 

 to bring the flashing room temperature in line with the room temperature

currently measured. The increments for the readjustment are 0.2°C {max. ±2 °C).
When balancing of the sensor is completed, the DIP switch must be reset to OFF.

Before cleaning the display or to prevent tampering, the display buttons can be locked.

Press the button behind the little hole for a short moment (max. 1 second): 

 ap-

pears and all other displays disappear. The display buttons are now disabled while all

the other functions are fully maintained.

Press the button behind the little hole again (max. 1 second).

Keep the button behind the little hole depressed for at least 3 seconds. This resets the
individual settings and the time of day to their default values. During the reset time of 3
seconds, the display will be fully lit, allowing the proper functioning of the display to be

checked. After each reset, all personal settings such as time of day, weekday, switch-
ing points, temperature setpoints, sensor calibration, etc., must be re-entered.

About three months before the batteries are exhausted, the display shows the battery
symbol 

. The other displays disappear, the display buttons are deactivated while

all the other functions are fully maintained. When changing the batteries, the current

data will remain stored for at least one minute.

Using a suitable remote operating unit, the REV100 can be switched to economy mode

. Changeover takes place by closing a 

SRWHQWLDOIUHHFRQWDFW

 connected to terminals

T1 and T2. In that case, symbol 

 appears on the display. When the contact opens,

the selected operating mode will be reactivated.

Operation according to controller setting

Continuous economy temperature

T2

T1

22

52

Z

05

T2

T1

22

52

Z

06

Suitable remote operating units: telephone modem, manual switch, window switch,
occupancy detector, control centre, etc.

Enter

Cancel

6HQVRUFDOLEUDWLRQ

/RFNLQJWKHGLVSOD\

Switching on

Switching off

5HVHW

%DWWHU\FKDQJH

5HPRWHFRQWURO

Remote operating units

Summary of Contents for REV100

Page 1: ...d consulting rooms or commercially used spaces For the control of the following pieces of equipment Solenoid valves of instantaneous water heaters Solenoid valves of atmospheric gas burners Heating circulating pumps zone valves normally closed Electric direct heating systems or fans of electric storage heaters XQFWLRQV PID control with self learning or selectable switching cycle Two different 24 h...

Page 2: ...ith a 3 switch and a relay with a potential free N O contact The connection terminals are integrated in the base 2211D11 5 1 2 6 3 4 7 Temperature values and symbols Normal temperature Economy temperature Standby with frost protection Time of day or switching time Change batteries Bumer in operation Remote control active Locking of display active Holiday program active Increasing decreasing values...

Page 3: ... three temperature setpoints but the values thus changed will be reset again when the next switching point is reached Press the time button and then to set the correct time of day The two switching points for the 24 hour operation with one heating period and the four switching points for the 24 hour operation with two heating periods can be entered individually and independently Operating mode Swi...

Page 4: ...intained Press the button behind the little hole again max 1 second Keep the button behind the little hole depressed for at least 3 seconds This resets the individual settings and the time of day to their default values During the reset time of 3 seconds the display will be fully lit allowing the proper functioning of the display to be checked After each reset all personal settings such as time of...

Page 5: ...ns that it automatically adapts to the type of controlled system type of building construction type of radiator size of room etc On completion of a certain leaming phase the con troller automatically optimizes its parameters and then operates based on the mode learned In exceptional cased where the self learning mode does not represent the optimum solution it is possible to choose PID 12 PID 6 or ...

Page 6: ...irective 89 336 EEC 73 23 EEC Electromagnetic compatibility Immunity Emissions EN 50 082 2 EN 50 081 1 Safety class II to EN 60 730 1 Degree of protection IP30 to EN 60 529 Perm ambient temperature Operation Storage and transport 3 35 C 25 60 C Perm ambient humidity G to DIN 40 040 Incl packing 0 3 kg Casing signal signal white RAL9003 Base grey RAL7038 Housing 120 x 98 x 31 mm 1RWHV The room temp...

Page 7: ...events inadvertent operation of the unit during trans port and storage must be removed The control characteristic can be changed with the DIP switch located at the rear of the unit If the reference room is equipped with thermostatic radiator valves they must be set to the fully open position If the room temperature displayed does not agree with the measured temperature the sensor should be re cali...

Page 8: ...as burner T 1 2222S03 0 Circulating pump with pre control by manual mixing valve F1 Thermal reset limit thermostat N1 REV11 room temperature controller F2 Manual reset safety limit thermostat Y1 Manually operated three port valve M1 Circulating pump Y2 Solenoid valve LPHQVLRQV 120 98 31 2222M01 83 5 30 30 13 30 30 10 2211M02 1999 Siemens Building Technologies Ltd Subject to change www landisstaefa...

Reviews: