Figure 7-7
Event Logs
Reading Fault Data from the HMI Screen
Fault indications are events which arise during a fault. Fault indications are triggered from the
Trip Config
parameter setting which must be set the trip contact. A fault is started by the incoming pickup of a protection
function and ends after the trip command with the cleared pickup.
Fault data records can be viewed on the HMI LCD with the time and date of the trip. These include the LED
status at the time of recording and the fault currents.
Available fault data is displayed in
Main Menu > Fault Data
in date and time format.
The number of faults stored is shown on the top of the LCD. If no faults have been stored the display will indi-
cate
No Faults to display
.
Previous fault data records are stored with actual LEDs status.
The fault data is displayed in date/time order with the most recent first.
i
i
NOTE
Trip Binary Output
must be configured as a trip contact from
Binary Outputs > Trip Config > Trip
Contacts
to initiate a fault record and trip screen.
7.4.5
In Service Operation
7.4 Indications
Reyrolle 7SR5, Operating, Manual
105
C53000-B7040-C013-1, Edition 05.2021
Summary of Contents for Reyrolle 7SR5
Page 6: ...6 Reyrolle 7SR5 Operating Manual C53000 B7040 C013 1 Edition 05 2021 ...
Page 10: ...10 Reyrolle 7SR5 Operating Manual C53000 B7040 C013 1 Edition 05 2021 ...
Page 40: ...40 Reyrolle 7SR5 Operating Manual C53000 B7040 C013 1 Edition 05 2021 ...
Page 76: ...76 Reyrolle 7SR5 Operating Manual C53000 B7040 C013 1 Edition 05 2021 ...
Page 114: ...114 Reyrolle 7SR5 Operating Manual C53000 B7040 C013 1 Edition 05 2021 ...