The COM-2 USB port has the IP address 192.168.2.1.
A Type-B
connection is required for a 7SR5 device and a Type-A
plug for a PC connec-
tion.
Connect to IP Address
Ethernet ports installed on the rear of the device can be used for IEC 61850 and Modbus TCP communications
to a substation SCADA, integrated control system, or engineer remote access using Reydisp Manager 2 config-
uration software.
[dw_7SR5_communication_to_rear_ethernet_port, 1, en_US]
Figure 5-13
Rear Ethernet Port Communication by IP Address
2 rear Ethernet ports (Standard) could be RJ45 electrical or LC optical duplex connector types (Fibre optic)
optionally with Channel 1 and Channel 2.
2 electrical (RJ45) ports (Channel 1/Terminal Reference X2 and Channel 2/Terminal Reference X3) or 2 optical
(LC) ethernet ports (Channel 1/Terminal Reference X4 and Channel 2/Terminal Reference X5).
The Ethernet port is unconfigured by default. IP addresses can be entered manually via the
Configure Inter-
face
menu in
Tasks
by the user.
•
IEC 61850, HSR , PRP and RSTP operation
•
Remote access to Reydisp Manager
If a device IP address assigned to an Ethernet port from the
Configure Interface
menu and send configuration
to the relay using the USB front port connection, then you could select the
Connect to IP Address
option for
selecting communication via the ethernet connected cable.
[sc_7SR5_DeviceConfigWindowSuccessUnsuccess, 1, --_--]
Figure 5-14
Sending Device Configuration Window With and Without Success
Using Reydisp Manager 2
5.3 Transmitting the Configuration to a 7SR5 Device for the First Time
70
Reyrolle 7SR5, Operating, Manual
C53000-B7040-C013-1, Edition 05.2021
Summary of Contents for Reyrolle 7SR5
Page 6: ...6 Reyrolle 7SR5 Operating Manual C53000 B7040 C013 1 Edition 05 2021 ...
Page 10: ...10 Reyrolle 7SR5 Operating Manual C53000 B7040 C013 1 Edition 05 2021 ...
Page 40: ...40 Reyrolle 7SR5 Operating Manual C53000 B7040 C013 1 Edition 05 2021 ...
Page 76: ...76 Reyrolle 7SR5 Operating Manual C53000 B7040 C013 1 Edition 05 2021 ...