Maintenance Password Configuration
The maintenance password is not active when the device leaves the factory or is returned to the factory condi-
tion. If a maintenance password has been activated it will be required to allow new firmware to be sent to the
device or the Security log to be accessed.
The maintenance password follows the NERC-CIP-standard (North American Electric Reliability Critical Infra-
structure Protection) and consists of the following parts:
•
Lower-case letters
•
Upper-case letters
•
Digits
•
Special characters, for example, %, &, $
The length of the maintenance password ranges from 8 characters to 24 characters.
The maintenance password is empty by default. To enter a new maintenance password, the existing charac-
ters are concealed by asterisks. To confirm the maintenance password, enter it twice. This confirmation
prevents erroneous entries.
[sc_7SR5_MaintenancePassword, 1, --_--]
Figure 9-4
Set Maintenance Password
Initialization of the maintenance password is possible only via the front USB interface or via an Ethernet inter-
face of the device. In both cases, the entered connection password is securely transferred to the device via the
HTTPS protocol. The connection password is not stored in the Reydisp Manager project or anywhere on the
Windows PC. It is stored as a salted hash in the device.
If you have initialized the maintenance password, this prevents unauthenticated upload of new firmware.
Siemens recommends checking the password after initialization.
You can change the connection password online via an Ethernet connection or the USB connection. After
entering the current connection password and entering and repeating the new connection password, the
device accepts the change.
9.6
Security Settings
9.6 Maintenance Password Configuration
Reyrolle 7SR5, Operating, Manual
139
C53000-B7040-C013-1, Edition 05.2021
Summary of Contents for Reyrolle 7SR5
Page 6: ...6 Reyrolle 7SR5 Operating Manual C53000 B7040 C013 1 Edition 05 2021 ...
Page 10: ...10 Reyrolle 7SR5 Operating Manual C53000 B7040 C013 1 Edition 05 2021 ...
Page 40: ...40 Reyrolle 7SR5 Operating Manual C53000 B7040 C013 1 Edition 05 2021 ...
Page 76: ...76 Reyrolle 7SR5 Operating Manual C53000 B7040 C013 1 Edition 05 2021 ...
Page 114: ...114 Reyrolle 7SR5 Operating Manual C53000 B7040 C013 1 Edition 05 2021 ...