RUGGEDCOM i802
Installation Guide
Chapter 6
Certification
EMC and Environmental Type Tests
23
Description
Test Levels
Enclosure Air
± 8 kV
Radiated RFI
Enclosure ports
35 V/m
Signal ports
± 4 kV @ 5 kHz
DC Power ports
± 4 kV @ 5 kHz
Fast Transient
Earth ground ports
± 4 kV @ 5 kHz
Signal ports
2.5 kV common mode @ 1MHz
Oscillatory
DC Power ports
2.5 kV common, 1 kV differential mode @ 1MHz
Environmental Type Tests
Test
Description
Test Levels
IEC 60068-2-1
Cold Temperature
Test Ad
-40 °C (-40 °F), 16 Hours
IEC 60068-2-2
Dry Heat
Test Bd
85 °C (185 °F), 16 Hours
IEC 60068-2-30
Humidity (Damp Heat, Cyclic)
Test Db
95% (non-condensing),
55 °C (131 °F), 6 cycles
IEC 60068-2-6
Vibration
1 g @ 10-500 Hz
IEC 60068-2-27
Shock
30 g @ 11 ms