Certification
6.2 EMC and Environmental Type Tests
•
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
6.2
EMC and Environmental Type Tests
The RUGGEDCOM RS401 has passed the following EMC and environmental tests.
IEC 61850-3 EMC Type Tests
Test
Description
Test Levels
Severi-
ty Lev-
els
Enclosure
Contact
±8 kV
4
IEC 61000-4-2
ESD
Enclosure Air
±15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
Signal Ports
±4 kV at 2.5 kHz
DC Power Ports
±4 kV
4
AC Power Ports
±4 kV
4
IEC 61000-4-4
Burst (Fast
Transient)
Earth
Ground Ports
±4 kV
4
Signal Ports
±4 kV Line-to-Earth,
±2 kV Line-to-Line
4
DC Power Ports
±2 kV Line-to-Earth,
±1 kV Line-to-Line
3
IEC 61000-4-5
Surge
AC Power Ports
±4 kV Line-to-Earth,
±2 kV Line-to-Line
4
Signal Ports
10 V
3
D.C Power Ports
10 V
3
AC Power Ports
10 V
3
IEC 61000-4-6
Induced (Con-
ducted) RFI
Earth
Ground Ports
10 V
3
IEC 61000-4-8
Magnetic Field
Enclosure Ports
40 A/m continuous,
1000 A/m for 1 s
DC Power Ports
30% for 0.1 s, 100% for 0.05 s
IEC 61000-4-29
30% for 1 period,
60% for 250 periods
IEC 61000-4-11
Voltage Dips
and Interrupts
AC Power Ports
100% for 5 periods,
100% for 50 periods
2
Signal Ports
2.5 kV common, 1 kV dif-
ferential mode at 1 MHz
3
DC Power Ports
2.5 kV common, 1 kV dif-
ferential mode at 1 MHz
3
IEC 61000-4-12
Damped
Oscillatory
AC Power Ports
2.5 kV common, 1 kV dif-
ferential mode at 1 MHz
3
38
RUGGEDCOM RS401
Installation Manual, 02/2020, C79000-G8976-1017-10