Certification
6.2 EMC and Environmental Type Tests
EMC Type Tests
Test
Description
Test Levels
Severi-
ty Levels
Enclosure
Contact
± 8 kV
4
IEC
61000-4-2
ESD
Enclosure Air
± 15 kV
4
IEC
61000-4-3
Radiated RFI
Enclo-
sure Ports
20 V/m
Signal Ports
± 4 kV @ 2.5 kHz
x
DC Pow-
er Ports
± 4 kV
4
AC Pow-
er Ports
± 4 kV
4
IEC
61000-4-4
Burst (Fast Transient)
Earth
Ground Ports
± 4 kV
4
Signal Ports
± 4 kV Line-to-Ground
± 2 kV
4
DC Pow-
er Ports
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
3
IEC
61000-4-5
Surge
AC Pow-
er Ports
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4
Signal Ports
10 V
3
DC Pow-
er Ports
10 V
3
AC Pow-
er Ports
10 V
3
IEC
61000-4-6
Induced (Conducted) RFI
Earth
Ground Ports
10 V
3
IEC
61000-4-8
Magnetic Field
Enclo-
sure Ports
40 A/m Continuous
1000 A/m for 1 s
IEC
61000-4-11
Voltage Dips and Interrupts
AC Pow-
er Ports
100% for 5 Periods
100% for 50 Periods
Signal Ports
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
3
DC Pow-
er Ports
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
3
IEC
61000-4-12
Damped Oscillatory
AC Pow-
er Ports
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
3
IEC
61000-4-16
Mains Frequency Voltage
Signal Ports
30 V Continuous
300 V for 1 s
4
RUGGEDCOM RS910
Installation Manual, 02/2020, C79000-G8976-1029-09
39