Chapter 6
Certification
RUGGEDCOM RSG2100PF
Installation Guide
40
EMC and Environmental Type Tests
Section 6.2
EMC and Environmental Type Tests
The RUGGEDCOM RSG2100PF has passed the following Electromagnetic Compatibility (EMC) and environmental
tests.
EMC Type Tests per IEC 61850-3
NOTE
• If the unit contains copper ports, the IEC 1613 conformance is Class 1, during which disturbance
errors may occur but recovery is automatic.
• If the unit contains all fiber ports, the IEC 1613 conformance is Class 2, during which no disturbance
errors will occur.
Test
Description
Test Levels
Severity Levels
Enclosure Contact
±8 kV
IEC 61000-4-2
ESD
Enclosure Air
±15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
Signal Ports
±4 kV @ 2.5 kHz
DC Power Ports
AC Power Ports
IEC 61000-4-4
Burst (Fast Transient)
Earth Ground Ports
±4 kV
4
Signal Ports
±4 kV Line-to-Ground,
±2 kV Line-to-Line
4
DC Power Ports
±2 kV Line-to-Ground,
±1 kV Line-to-Line
3
IEC 61000-4-5
Surge
AC Power Ports
±4 kV Line-to-Ground,
±2 kV Line-to-Line
4
Signal Ports
DC Power Ports
AC Power Ports
IEC 61000-4-6
Induced (Conducted) RFI
Earth Ground Ports
10 V
3
IEC 61000-4-8
Magnetic Field
Enclosure Ports
100 A/m Continuous
1000 A/m for 1 s
5
IEC 61000-4-11
Voltage Dips
and Interrupts
AC Power Ports
30% for 1 period
60% for 50 periods
100% for 5 periods
100% for 50 periods
Signal Ports
DC Power Ports
IEC 61000-4-12
Damped Oscillatory
AC Power Ports
2.5 kV Common
1 kV Differential
Mode @1 MHz
3