RUGGEDCOM RX1000
Installation Guide
Chapter 6
Certification
EMI and Environmental Type Tests
43
Test
Description
Test Levels
Severity Levels
Signal ports
2.5 kV common,
1 kV differential
mode @ 1 MHz
3
DC Power ports
2.5kV common,1kV
differential
mode @ 1 MHz
3
IEC 61000-4-12
Damped Oscillatory
AC Power ports
2.5 kV common,
1 kV differential
mode @ 1 MHz
3
Signal ports
30 V Continuous,
300 V for 1 s
4
IEC 61000-4-16
Mains Frequency Voltage
DC Power ports
30 V Continuous,
300 V for 1 s
4
IEC 61000-4-17
Ripple on DC
Power Supply
DC Power ports
10%
3
Signal ports
2 kVAC (Fail-
Safe Relay output)
DC Power ports
1.5 kVDC
Dielectric Strength
AC Power ports
2 kVAC
Signal ports
5 kV (Fail-Safe
Relay output)
DC Power ports
5 kV
IEC 60255-5
HV Impulse
AC Power ports
5 kV
a
Siemens-specified severity levels
b
Only applicable to functional earth connections separated from the safety earth connection.
IEEE 1613 (C37.90.x) EMI Immunity Type Tests
NOTE
The RX1000 meets Class 2 requirements for an all-fiber configuration and Class 1 requirements for
copper ports.
Test
Description
Test Levels
Enclosure Contact
+/- 8 kV
IEEE C37.90.3
ESD
Enclosure Air
+/- 15 kV
C37.90.2
Radiated RFI
Enclosure ports
35 V/m
Signal ports
+/- 4 kV @ 2.5 kHz
DC Power ports
+/- 4 kV
AC Power ports
+/- 4 kV
Fast Transient
Earth ground ports
+/- 4 kV
Signal ports
2.5 kV common mode @ 1 MHz
IEEE C37.90.1
Oscillatory
DC Power ports
2.5 kV common and
differential mode @ 1 MHz