120/166
Siemens Building Technologies
Basic Documentation RVA47.320
CE1P2379E
HVAC Products
Description of the OEM settings
15.07.2002
The pump’s running time is set to a minimum of 3 minutes.
The pump’s off time is set to a minimum of 2 minutes.
Also, the pump will be activated and deactivated at the following switching points:
•
Pump continuously ON TVxGed
≤
TVwGef (
ε
≥
1)
•
Pump continuously
OFF
TVwGef
≤
TRw
<
TVxGed
The function of a room temperature sensor - if present - overrides that of the
overtemperature protection.
5.11 Heat
gains
•
To save energy, heat gains are taken into consideration
This setting takes into account potential heat gains from machines, pieces of
equipment, or other constant heat sources, that might adversely affect accurate control.
The value will change when the heating curve adaption is activated.
1.
Press the line selection buttons to select line 35OEM.
2.
Press the + / - buttons to set the effect of heat gains.
Setting range
Unit
Factory setting
-2...+4 °C
0
The setting compensates the sum of all constant heat gains as follows:
Increase:
For more compensation
In the case of significant heat sources
Decrease:
For less compensation
In the case of less significant heat sources
The setting in °C corresponds to the temperature differential that would result if the
room was solely heated by the heat gains.
5.12
Adaption sensitivity 1
•
Adaption of the heating curve as a function of the outside temperature
Adaption sensitivity 1 serves for calculating the adaption of the heating curve in the
temperature range 4 to 12 °C (also refer to section "Adaption of heating curve, line
106”).
1.
Press the line selection buttons to select line 36OEM.
2.
Press the + / - buttons to adjust adaption sensitivity 1.
Display
Factory setting
1...15 15
Limitations
Important
Benefit
Description
Setting
Effect
Benefit
Description
Setting