147/166
Siemens Building Technologies
Basic Documentation RVA47.320
CE1P2379E
HVAC Products
Application examples
15.07.2002
8.3
Plant types RVA47.320 - no. 29
The plant type no. is identical with the number displayed on line 53.
Control of a single BMU or cascade control of up to four BMUs. D.h.w. heating by one
BMU, with changeover valve.
4
1
2
3
B10
23
79
S
29
B70
Type of unit
BMU 1
BMU 2
BMU 3
BMU 4
RVA47.320
Display of plant type
29
Heating curve (line 17)
--- (inactive)
Pump function Q1 (line 95)
1 (heating circuit
pump or no pump)
This application requires the heat demand signal from a consumer to release heat
generation:
•
LPB capable controllers signal the RVA47.320 their current heat demand directly
via LPB.
•
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.
A heat demand signal from the d.h.w. storage tank releases only that boiler to which
the storage tank is hydraulically connected. The other boilers of the cascade will not be
released.
N1
B3
B9
B70
B70
M
L
N
23
79
A
27
MB
LPB
MD
A6 / BMU
PPS
DB
B10
B
M
H1
B10
B
M
B9
B
M
A6
B
M
H1
Q1
F1
Q3
L
N
The d.h.w. sensor (B3) is connected directly to BMU 1.
For a detailed legend, refer to page 158.
Note
Hydraulic circuit
Important
Note
Electrical connections
Note