Siemens Building Technologies
Basic Documentation RVA47.320
CE1P2379E
HVAC Products
Technical data
15.07.2002
10 Technical
data
Nominal voltage
AC 230 V (±10 %)
Nominal frequency
50 Hz (±6 %)
Power consumption
max. 7 VA
Safety class
II, to EN 60 730
(when mounted properly)
Degree of protection
IP 40 to EN 60 529
(when mounted correctly)
Electromagnetic immunity
conforming to the requirements of
EN 50 082-2
Electromagnetic emissions
conforming to the requirements of
EN 50 081-1
Operation to IEC 721-3-3
lass 3K5 (noncondensing)
Temperature 0...50
°C
Storage to IEC 721-3-1
class 1K3
-25…70 °C
Transport to IEC 721-3-2
class 2K3
-25…70 °C
To EN 60 730
usual environment
Operation to IEC 721-3-3
class 3M2
Storage to IEC 721-3-1
class 1M2
Transport to IEC 721-3-2
class 2M2
To EN 60730 par. 11.4 11.4
1b
Voltage range
AC 24...230 V
Nominal current
AC 0.02…2 (2) A
Switch-on peak
max. 10 A for max. 1 s
Fusing max.
10
A
Perm. cable length for PPS:
(Telephone wire 0.8 mm dia., 2-wire
interchangeable)
Max. cable length central unit / peripheral unit
75 m
Max. total cable length (sum of all branches)
250 m
Perm. cable length for LPB:
(copper cable 1.5 mm
2
, 2-wire
not
interchangeable)
With controller bus power supply (per controller)
250 m
With central bus power supply (bus power supply
/ controller)
460 m
Bus loading number
E = 3
0.6 mm dia.
max. 20 m
1.0 mm
2
max. 80 m
1.5 mm
2
max. 120 m
Power supply
Requirements
Climatic conditions
Contamination
Mechanical conditions
Mode of operation
Output relays
Bus extension
Perm. sensor cable
lengths