71/166
Siemens Building Technologies
Basic Documentation RVA47.320
CE1P2379E
HVAC Products
Description of the heating engineer settings
15.07.2002
00.1...16.3 Device
address and device subaddress (boiler number in a controller) of
the boilers assigned to the system (max. 16).
All boilers must be contained in segment 0 to ensure the demand for
heat from all segments will be considered.
Do not mix up device / device subaddress and segment / device address!
If the segment address was added, the display would read 0.00.1 ... 0.16.3.
A controller that uses device address 0 (e.g.
00
.1) operates autonomously ( no
communication via LPB).
The device address 1 (
01
.1) defines the cascade master (controller).
Up to four BMUs can be connected to the first RVA47.320 (B-series) of a cascade, and
up to three BMUs to each of the additional RVA47.320 (B-series).
The possible device subaddresses are therefore 1.
1
... 1.
4
, 2.
1
... 2.
3
, 3.
1
... 3.3
through 16.3 One cascade can contain a maximum of 16 boilers, however.
The setting for boiler sequence changeover is made on operating line 130.
For more detailed information, refer to ”Local Process Bus (LPB), Basic
Documentation, System Engineering” (document no. CE1P2370E).
4.21
Remaining number of operating hours for
changeover of boiler sequence
•
Indication of the remaining number of operating hours until the next changeover of
boiler sequence takes place.
Indicates the number of hours the current lead boiler still operates until the next
changeover of boiler sequence occurs.
When selecting this operating line, the remaining number of operating hours for
changeover of the boiler sequence are displayed.
Display
Unit
0...990 / ---
h / -
The number displayed represents the number of operating hours until the next
changeover of boiler sequence occurs. It is generated by subtracting the current
number of operating hours from the setting made on operating line 130 (automatic
changeover according to the number of operating hours).
The display appears only if, on operating line 130, a setting of 10…990h has been
selected (automatic changeover according to the number of operating hours).
Otherwise, the display will show "- - -”.
Caution!
Device address
Device subaddress
Note
Benefit
Description
Setting