Quick setback with room sensor
Making use of the building’s thermal storage capacity.
Quick setback is dependent on whether or not a room temperature sensor is used. A
differentiation must therefore be made between quick setback with or without room
sensor.
Important
This process has an impact only when a room sensor is used.
Quick setback is started as soon as a change to a lower room temperature setpoint
takes place (e.g. switching times in automatic mode).
Quick setback is terminated as soon as the actual room temperature reaches the level
of the respective room temperature setpoint (TRx = TRw).
20
15
°C
t
TRx
23
71
D
0
8
TRw
ON
OFF
H
t
TRx
Actual value of the room temperature
TRw
Room temperature setpoint
H
“Quick setback” function
Due to the readjustment of the room temperature setpoint, the heating circuit pump will
be switched off until the quick setback process is terminated. This means that the room
temperature falls quicker since the supply of heat from the boiler is cut off.
If no room sensor is connected, quick setback will not be accomplished through this
process. Also refer to “constant for quick setback” in Index.