25/184
Siemens Building Technologies
Basic Dokumentation RVA63.280, RVA53.280
CE1P2374E
Landis & Staefa Division
19.04.2001
2.5.1
Overview of heating engineer parameters
RVA
6
3
.2
8
0
RVA
5
3
.2
8
0
Func
ti
o
n
Ra
n
g
e
Un
it
R
esol
u
tio
n
F
a
ct
o
ry
set
ti
ng
Service values
51
51
Output test
0
Control mode according to the operating state
1
All outputs OFF
2
Burner stage 1 ON
K4
3
Burner stages 1 and 2 ON
K4 / K5
4
D.h.w. charging pump ON
Q3/Y3
D.h.w. diverting valve OPEN
Q3 / Y3
5
Heating circuit pump 1
Q2
6
Mixing valve 1 open
Y1
7
Mixing valve 1 close
Y2
8
Heating circuit pump 2
Q6
9
Mixing valve 2 open
Y5
10
Mixing valve 2 close
Y6
0...10
-
1
0
52
52
Input test
0
Boiler sensor
B2
1
D.h.w. sensor 1
B3
2
Display of input B31/H2
B31
3
Flow sensor HC1
B1
4
Flow sensor HC2
B12
5
Outside sensor
B9
6
Room sensor 1
RG1, A6
7
Room sensor 2
RG2, A7
8
Flue gas sensor
B8
9
Display of input H1
H1
0...9
-
1
0
53
53
Display of plant type
1...127
-
1
-
Actual values
55
55
Actual value of flow temperature (TVx)
Input B1/B12
0...140
°C
1
-
56
56
Actual value of boiler temperature (TKx)
Input B2/B4
0...140
°C
1
-
57
-
Actual value of common flow temperature
0...140
°C
1
-
61
61
Actual value 1 of d.h.w. temperature (TBWx)
(Higher temperature)
0...140
°C
1
-
62
62
Actual value 2 of d.h.w. temperature (TBWx)
(Lower temperature)
0...140
°C
1
-
63
63
Display of maximum flue gas temperature
(TGxmax)
To make a reset to the current value, press the + and –
buttons simultaneously for 3 seconds
0...350
°C
1
-
65
65
Attenuated outside temperature
(TAxged)
-50...+50
°C
0.5
-
66
66
Composite outside temperature
(Taxgem)
-50...+50
°C
0.5
-
67
-
Outside temperature source
- - . - -
No signal
00.01...14.16
Address
- -:- / 00.01...14.16
-
1
-
Setpoints
68
68
Display of boiler temperature setpoint
0...140
°C
1
-
69
-
Display of common flow temperature setpoint
0...140
°C
1
-
70
70
Display of d.h.w temperature setpoint
0...140
°C
1
-
71
71
Display of nominal room temperature
setpoint
Nominal setpoint incl. room unit readjustment
0...35
°C
0,5
-
73
73
Display of room temperature setpoint (TRw)
0...35
°C
0,5
-
75
75
Display of flow temperature setpoint
0...140
°C
1
-