27/184
Siemens Building Technologies
Basic Dokumentation RVA63.280, RVA53.280
CE1P2374E
Landis & Staefa Division
19.04.2001
RVA
6
3
.2
8
0
RVA
5
3
.2
8
0
Func
ti
o
n
Ra
n
g
e
Un
it
Res
o
lu
ti
o
n
F
a
ct
o
ry
set
ti
ng
116
-
Floor curing
0
Off
1
Functional heating
2
Floor curing
3
Functional and floor curing heating
0...3
-
1
0
D.h.w.
120
120
Reduced setpoint of d.h.w. temperature (TBWR)
TBWw
Line 26
8...TBWw
°C
1
40
121
121
D.h.w. heating program
0
24 h/day
1
Heating program with forward shift
2
Time switch program 3
0...2
-
1
1
123
-
Assignment of d.h.w. heating
0
Local heating circuit
1
All heating circuits in the segment
2
All heating circuits in the system
0...2
-
1
2
124
124
D.h.w. charging
0
Once per day with a forward shift of 2.5 hours
1
Several times per day with a 1 h forward shift
0 / 1
-
1
1
125
125
Type of d.h.w. demand
0
Sensor
1
Control thermostat
0 / 1
-
1
0
126
126
Boost of the flow temperature setpoint for d.h.w.
heating (UEBW)
0...30
°C (K)
1
16
127
127
D.h.w. priority
0
Absolute (mixing and pump heating circuit)
1
Shifting (mixing and pump heating circuit)
2
None (parallel)
3
Mixing heating circuit (shifted)
Pump heating circuit (absolut)
0...3
-
1
1
128
128
Controlling element for d.h.w.
0
Charging pump
1
Diverting valve
0 / 1
-
1
0
LPB / system
140
-
LPB device address
0
Standalone
1...16
Device address (system)
0...16
-
1
0
141
-
LPB segment address
0
Heat source segment
1...14
Heat consumption segments
0...14
-
1
0
142
-
LPB power supply
0
Off (central bus power supply
1)
Auto (bus power supply via controller)
0 / 1
-
1
1
143
-
Display of LPB power supply
On / OFF
-
-
145
-
Range of action of central changeover
0
In the segment
1
In the system (if segment address = 0)
0 / 1
-
1
1
146
-
Automatic summer / winter changeover
0
Local changeover
1
Central changeover of all heating circuits
0 / 1
-
1
0
147
-
Central stand-by switch
1)
0
Off
1
ON
0 / 1
-
1
0
148
-
Clock mode
0
Autonomous clock
1
System time without adjustment
2
(System time with adjustment)
3
System clock (master)
0...3
-
1
0