37/130
Siemens Building Technologies
Basic Documentation RVD230
CE1P2383en
HVAC Products
11 Function block Plant configuration
27.05.2004
•
Setting 2: The RVD230 can receive a DC 0…10 V signal from a plant element and
then pass it on via M-bus. Plant element can be a differential pressure sensor, for in-
stance. The signal has no impact on the control functions of the RVD230
•
Setting 3: B71 / U1 acts as a scalable DC 0…10 V input to receive the heat demand
signals from other devices
11.2.3 Circulating
pump
The circulating pump is to be configured on operating line 54.
0 = no circulating pump present
1 = the circulating pump feeds water into the storage tank; this takes place only when
d.h.w. heating is activated
2 = the circulating pump feeds water into the heat exchanger’s secondary return, whe-
reby 80 % of the heat losses will be compensated for
3 = the circulating pump feeds water into the heat exchanger’s secondary return, whe-
reby 100 % of the heat losses will be compensated for
When using setting 2 or 3, the circulating pump runs during the whole period of time
d.h.w heating is released (also refer to subsection 17.3.6 "Compensation of heat losses
through control".
11.2.4 Input H5
Terminal H5 of the RVD230 is a digital input. It offers the following choices:
0 = no function
1 = reception of pulses.
For more information, refer to chapter 28 “Function block Miscellaneous" (operat-
ing lines 181 through 183)
2 = reception of heat demand signals.
For more information, refer to chapter 14 “Function block Valve actuator heat con-
verter / primary controller" (operating lines 87 and 88)
3 = input for alarm signals. It is possible to receive error messages in the form of pul-
ses; operating line 50 displays them with error code 171; they can be passed on
via LPB or M-bus
4 = input for flow switch. To improve the control performance, it is possible to fit an
optional flow switch in the d.h.w. circuit of several types of plant; with plant type 8–
4, the use of a flow switch is mandatory
The unit connected to H5 must have gold-plated contacts; if AC 230 V has passed
through such contacts, they cannot be used again.
11.2.5 Control of variable speed pump
The RVD230 features a pulse-width-modulated output that is used for the control of a
variable speed pump. Based on the temperature conditions, the controller calculates
the ideal speed of the pump. The speed-controlled pump is to be selected on operating
line 57. This can be:
Setting Terminal Used
as:
1
Q1
Heating circuit pump
2 Q2
Heating circuit pump with plant type 7–2,
storage tank charging pump in connection with stratification
storage tanks with plant type 3–7
3 Q3
Intermediate circuit pump in connection with coil type storage
tanks
4 Q4
Storage tank charging pump in connection with stratification
storage tanks
In manual operation, the speed-controlled pump runs at the nominal speed.
Use