Building Technologies
74 319 0619 0 a
17.04.2008
50/288
en
69 Maximum limitation
of room temperature
--.- °C
(--.- / 0…35)
...................
°C
Setting --.- = limitation deacti-
vated
Function possible only with
room unit / room temperature
sensor
70 Effect of room tem-
perature
4
(0…20)
.........................
Gain factor for effect of room
temperature
Function possible only with
room unit / room temperature
sensor
71 Boost of room tem-
perature setpoint
with boost heating
5 °C
(0…20)
...................
°C
72 Parallel displace-
ment of heating
curve
0.0 °C
(
−
4.5…+4.5)
...................
°C
Value in °C room temperature
73 Type of heating
curve adjustment
0
(0…2)
.........................
0 = analog adjustment
1 = digital adjustment on the
controller and via bus
2 = digital adjustment via bus
only
Block “3-position actuator for heating circuit”
81 Maximum limitation
of flow temperature
--- °C
(--- / 0…140)
...................
°C
Setting --- = function deacti-
vated
No safety function
82 Minimum limitation
of flow temperature
--- °C
(--- / 0…140)
...................
°C
Setting --- = function deacti-
vated
83 Maximum rate of
increase of flow
temperature
--- °C/h
(--- / 1…600)
..............
°C/h
Setting --- = function deacti-
vated (function prevents crack-
ing noise in piping)
84 Excess flow tem-
perature mixing
valve
10 °C
(0…50)
...................
°C
Setpoint boost for precontroller
in interconnected plants
85 Actuator running
time
120 s
(30…873)
......................
s
For latest prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk - info@mytub.co.uk 0844 556 1818