Building Technologies
74 319 0619 0 a
17.04.2008
57/288
en
142 Outside
tempera-
ture switch
Switch-off value for
occupancy time
0
(0 / 1)
.........................
0 = relay DEENERGIZED
1 = relay ENERGIZED
Function can be provided only
when operating line 141 = 7
143 Outside
tempera-
ture switch
Switch-off value for
non-occupancy time
5.0 °C
(
−
35.0…+35.0)
...................
°C
Function can be provided only
when operating line 141 = 1
144 Outside
tempera-
ture switch
Switching differen-
tial
−
5.0 °C
(
−
35.0…+35.0)
...................
°C
Function can be provided only
when operating line 141 = 1
145 Selection
time
switch
3 °C
(1…20)
...................
°C
Function can be provided only
when operating line 141 = 1
146 Outside
tempera-
ture switch
Switch-off value for
occupancy time
3
(1…3)
.........................
1 = heating program
2 = switching program 2
3 = switching program 3
Block “Legionella function”
147 Periodicity of le-
gionella function
1
(0…7)
.........................
0 = daily
1…7 = weekly, whereby
1 = always on Monday
2 = always on Tuesday; etc.
148 Time for charging
05:00
(00:00…24:00)
.........................
149 Dwelling time at
legionella setpoint
30 min
(0…360)
................
min
For setpoint of legionalla func-
tion, refer to line 130
150 Circulating
pump
operation during
legionella function
1
(0 / 1)
.........................
0 = no impact on the circulating
pump
1 = with impact on the circulat-
ing pump
For latest prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk - info@mytub.co.uk 0844 556 1818