34/46
Siemens
Heating controllers RVP201 and RVP211
CE1P2464en
Building Technologies
4 Handling
2017-07-21
Function
Switch position "left"
Symbol
Switch position "right"
Type of regulating unit Control of a motorized
seat or slipper valve
Control of a burner (at-
mospheric or forced
draught)
Type of control
Three-position (modulat-
ing)
Two-position (on/off)
Frost protection
Yes, frost protection
No, no frost protection
Priority of d.h.w. heat-
ing (only with the
RVP211)
With priority (absolute).
Underfloor heating sys-
tems and boiler opera-
tion: always use "abso-
lute"!
No priority (parallel)
RVP211 with boiler temperature control:
Regulating unit for
d.h.w. heating
Changeover valve
Charging pump
In the case of boiler temperature control with the RVP211, coding switch "Type of con-
trol" is used for entering the d.h.w. regulating unit.
The factory-set value (default value) is marked by a dot . This value can be used as a
guide value. If no plant-specific settings are available, the factory settings should be
used.
Potentiometer Function
Setting range
Guide values, notes
Switching differen-
tial with two-position
control
1…20 K
Effective only with burner
control:
guide value 6 K
Effect of room tem-
perature on flow
temperature control
0…100 % authority
Guide value for plants with
outside sensor: 50 %
Quick setback is
active/ inactive
Off
Off = quick setback is inac-
tive
Heating limit for
ECO automatic
energy saver
–10…+ 8 K
The setting refers to
the room tempera-
ture setpoint
At 20 °C room tempera-
ture, the default value of
–3 K gives a heating limit
of 17 °C.
To disable the function: set
to Off
Maximum limitation
of flow or boiler
temperature
10…100 °C
Guide value for underfloor
and ceiling heating sys-
tems: 55 °C max.
To disable the function: set
to Off
4.1.2 Setting and readjusting the room temperature
To make the basic setting and to readjust the room temperature, there are two setting
elements available:
For setting the heating curve slope, use setting knob
For manual readjustment of the room temperature, use setting knob
; its scale
gives the room temperature differential in °C; this setting produces a parallel dis-
placement of the heating curve
Coding switches
Note
Setting potentiometer