background image

Siemens Building Technologies 

A6V10464930_enGB_

a

b   

 

 

2017-03-09 

1/2

 

 

 

RWB29Si Installation instruction 

 

 
Please take a little time to fully read these installation and user instructions so as to gain the most from your RWB29Si. 

1. Programme Choice 

To enable you to select the programme most suitable for your needs we offer a choice of 3 programmes: 
 

Daily; Which means the unit will come ON and go OFF at the same times each day. 

Weekday/Weekend; Which means the unit can be altered for weekdays and weekends. 

7 Day; Which means the unit can be set to come ON and go OFF differently on every or any day. 

 
Please refer to the dipswitch positions on below section dipswitches 

 

2. Dipswitches 

To change the dipswitch positions first switch off the mains supply and then remove the unit from its backplate by simply loosen-
ing the two screws and pulling towards you. 
 

Program choice 

with DIP# 1, 2 & 3

 

ON/OFF switching periods 

with DIP# 4

 

System type 

with DIP# 5

 

1    2     3    4    5

 

ON

OFF

 

Daily 

 

Two ON/OFF periods per day 

 

Gravity system (10) 

1    2     3    4    5

 

ON

OFF

 

Weekday/Weekend 

 

Three ON/OFF phases per day 

 

Fully pumped system (16) 

1    2     3    4    5

 

ON

OFF

 

7 Day 

 

 

 

 

 
When you have completed the changes to the dipswitches, replace the unit onto its backplate and then refer to the booklet sup-
plied with the unit that relates to the programme you have selected: Daily Programming, Weekday/Weekend Programming or 
7 Day Programming. 

 
This leaflet will help you to install and commission your programmer easily and quickly. 

3. Installation 

1. 

First remove the backplate from the RWB29Si

 by undoing the two small screws at the base of the unit and lift out from the 

bottom so that the two lugs at the top disengage from their positions. 
 

2. 

The RWB29Si is factory set to provide 2 on/off switching periods per day and each day will be the same

, i.e. daily 

operation. To select the other styles of switching you will have to alter the dip switches which are to be found at the bottom 
rear of the unit (see Fig. 1) into the relevant position for the style of operation you require. See section 2 for dip[ switch set-
ting.  

Note:

 Press RESET after any dip switch change. 

 

3. 

Once you have completed the above you are now ready to connect the RWB29Si to the backplate

, If the RWB29Si is 

replacing another Landis & Gyr or Landis & Staefa product as listed below no wiring changes are required, RWB1, RWB2, 
RWB20, RWB40, RWB200, RWB200cw, RWB252, RWB252cw, RWB270, RWBXP, Gloworm Mastermind, Potterton 
Miniminder, Sankey Sunline. 
 

4. 

If the RWB29Si is replacing another Landis & Gyr or Landis & Staefa product as listed below

, these products are NOT 

suitable for replacement by the RWB29Si. Return the RWB29Si to your stockist/installer and request the RWB27Si which will 
fully interface with your old unit’s backplate. with the exception of the RWB3 which will require a link inserted from L to 2 on 
the existing backplate RWB3, RWB7, RWB30, RWB50, RWB100, RWB152, RWB152cw, RWB170 and RWBXT. 
 

5. 

Mounting Location

 

To ensure convenience of use, the RWB29Si should be fitted in a position which allows easy access. It is recommended that 
the unit is placed at a height of 1.4 meters’ from the floor, and should not be installed where either extremes of heat or cold 
exist. Care should also be taken to ensure that steam, water or oil cannot splash onto or enter either the RWB29Si or its 

 

 

Reviews: