Display explanation
Name
Description
Display, Setting Range
Name
Description
Display, Setting Range
General Screen
Adjustable setpoint page
TOOL
PC communication port being used
#
10
Application No
10…79 (Not consecutive
numbers)
OUT
RANGE
The setting is out of range
!
Day time operation
Err
Sensors error
Night time operation
#10
★
★
=
Using not the defaulted sensor
X1
Universal (Main) Input X1
•
Ni 1000
Ω
: -50…150°C
(unchangeable)
•
Pt 1000
Ω
: -20…180°C
(unchangeable)
•
0-10 Vdc: -100…8000
WIN/SUM
Winter/Summer mode being chosen
or activated
X2
Universal (Auxiliary) Input X2
•
Ni 1000
Ω
: -50…150°C
(unchangeable)
•
Pt 1000
Ω
: -20…180°C
(unchangeable)
•
0-10 Vdc: -100…8000
•
Variable resistor: the
resistance range should
within 0…1000
Ω
LIM
Limiter mode being chosen or
activated
K
Kelvin
REM
Remote setpoint mode being chosen
or activated
%
Percentage scale (e.g. RH)
COMP
Setpoint compensation mode being
chosen or activated
----
No unit (e.g. pressure, air
quality and air volume flow)
CAS
Cascade mode being chosen or
activated
Sec
Second
MaxPrior
Maximum priority mode being
chosen or activated
Q1
Digital output 1
■
is on; is off
SP-h
Setpoint on the heating side for
temperature control
Q2
Digital output 2
■
is on; is off
SP-c
Setpoint on the cooling side for
temperature control
On
On status
SP-r
Setpoint on the reverse acting side
for active input (0…10 Vdc)
Off
Off status
SP-d
Setpoint on the direct acting side for
active input (0…10 Vdc)
°C
Celsius scale
XDZ
•
For R or D independent loops.
Day setpoint offset from the first
output to the second output when
in REM mode.
•
For R+D application. Dead zone
between R and D day setpoints
when in REM mode.
•
Ni: 0.5…180 K
•
Pt: 0.5…180 K
•
Active input:
0.05…7300
°F
Fahrenheit scale
>
>>
>
I
II
I
K
KK
K