Siemens Building Technologies
CE1G3343de,en
26.08.2009
7/8
en
Menu and display
Main display
Access to info displays
▲
or
▼
Access to setting displays
▲
and
▼
for 5 sec.
Heating and/or cooling
setpoints for “Comfort“
mode
(Q1 and Y1)
Level 4:
Main loop settings
Heating and/or cooling
setpoints for “Econ-
omy“ mode (Q1 and
Y1)
Level 3:
Auxiliary functions
settings
Sensor value (X2)
for auxiliary function
Level 2:
Sensors settings
Modulating output
value (Y1)
Level 1:
Application number
Relay output status
(Q1)
Current application
Parameter
Description
Level
0-10
Active sensor
DC 0…10 V
PS2
#10 … #89
Application number
PS1
Δ
X1 /
Δ
X2
Sensor offset
PS2
ABS
Absolute limitation
function
PS1
Act
Active sensor
DC 0…10 V
PS1
AnLG
Winter/summer
change-over with
temperature sensor
PS1
CAS
Cascade function
PS1
COMP
Compensation function PS1
diG
Winter/summer
change-over with
thermostat
PS1
EXIT
Exit commissioning
menu
PS4
H
Highest value for sen-
sor measuring range
PS2
L
Lowest value for sen-
sor measuring range
PS2
LIM
Limitation function
PS1
LS
Ni 1000 Siemens
sensor
PS2
Maximum value for
limitation function
PS3
MAX
Output end point for Y1 PS4
MAXPRIOR
Maximum priority
function
PS1
MIN
Minimum value for
limitation function
PS3
Parameter
Description
Level
Output starting point
for Y1
PS4
Q1 ON
Q1 switched on
PS4
Pt
Pt 1000 sensor
PS2
rEL
Relative limitation
function
PS1
REM
Remote setpoint setting PS1
SD
Switching differential
PS4
SUM
Summer change-over
temperature setpoint
PS3
T
Time delay for Winter /
Summer change-over
PS3
T1
Minimum switch off
PS4
TN-h / TN-r
Integration time for
heating (\ reverse)
sequence
PS4
TN-c / TN-d
Integration time for
cooling (/ direct) se-
quence
PS4
UNT
Sensor value units
PS2
VR
0…1000
Ω
signal
PS2
WIN
Winter change-over
temperature setpoint
PS3
XDZ
Neutral zone
PS4
XP-h / XP-r
Proportional band for
heating (\ reverse)
sequence
PS3
PS4
XP-c / XP-d
Proportional band for
cooling (/ direct) se-
quence
PS3
PS4
Confort mode
PS4
Economy mode
PS4