background image

 

 
 
 
 
 

RWD68U 

Technical Instructions

Document No. 155-738

January 14, 2005

 

Universal Controller 
 

 

 

 

Description 

The Universal Controller is intended for heating, air conditioning, ventilation and 
refrigeration in comfort control applications. RWD68U main loop control applications 
are designed for temperature, static pressure, humidity, air pressure, fluid pressure, 
refrigeration, air quality and air fluid velocity control. The controller contains pre-
programmed applications. 

Auxiliary control functions include:  

• 

Day/night setpoints 

• 

Remote setpoint control 

• 

Limiter control 

• 

Cascade control 

• 

Maximum priority 

• 

Setpoint compensation 

• 

Summer/winter operation 

Control parameters are adjusted for maximum comfort control via three buttons on the 
face of the device, or with a laptop computer and Siemens Building Technologies 
program software. 

NOTE: 

For complete supporting technical documentation, including training 
presentations, see www.us.sbt.siemens.com/hvp/components. 

Features 

• 

Stand-alone electronic temperature controller with P or P+I response 

• 

24 Vac operating voltage 

• 

Control application selectable via Application Number 

• 

Active input scale can be selectable 

• 

Limit and direction of the output scale can be freely assigned 

• 

Two universal inputs for Siemens 1000 ohm nickel (Ni 1000), 1000 ohm platinum 
(Pt 1000) temperature sensors and 0 Vdc to 10 Vdc signals 

• 

Unit can be set as °F, °C, % or no specified unit 

• 

One modulating 0 to 10 Vdc signal output, direct or reverse action 

• 

One two-position output, direct or reverse action 

• 

One digital input for day/night changeover 

• 

Entering or changing of all data via operating buttons on the controller, is possible 
without additional tools 

• 

Computer connection for downloading pre-programmed applications via the 
software tool 

Product Number 

RWD68U 

Siemens Building Technologies, Inc. 

Summary of Contents for RWD68U

Page 1: ...gies program software NOTE For complete supporting technical documentation including training presentations see www us sbt siemens com hvp components Features Stand alone electronic temperature controller with P or P I response 24 Vac operating voltage Control application selectable via Application Number Active input scale can be selectable Limit and direction of the output scale can be freely as...

Page 2: ... to 916 Energy Management Equipment Terminals Screw terminals min max conductors Minimum 24 AWG 1 Maximum 16 AWG 2 or 14 AWG 1 Weight RWD68U Controller 10 72 oz 304 grams With packaging 12 64 oz 358 grams Analog Inputs X1 X2 Siemens Ni 1000 ohm 32 F 0 C Controller measuring range 58 F to 302 F 50 C to 150 C Maximum cable length for 14 AWG 984 ft 300 m Pt 1000 ohm at 32 F 0 C Controller measuring r...

Page 3: ...5 155 177P25 GEB Series 132 in lb Non Spring Return Actuators 155 318P25 GCA Series 142 in lb Spring Return Actuators 155 173P25 155 174P25 155 175P25 GMA Series 62 in lb Spring Return Actuators 155 315P25 SKD Valve Actuator with proportional input SKD Valve Actuator with floating input 155 180P25 155 181P25 SKB SKC Valve Actuator with proportional input SKB SKC Valve Actuator with floating input ...

Page 4: ...se acting independent and dependent control loop or Y2 and Q1 Direct and direct acting independent and dependent control loop NOTE Direct Acting As air temperature increases the control output increases Reverse Acting As air temperature increases the control output decreases TH0599R3 TEMPERATURE SENSOR AIR DAMPER ACTUATOR HEATING COIL COOLING COIL HEATING OR COOLING COIL TWO PIPE FAN OR PUMP TIME ...

Page 5: ... or a 0 to 10 Vdc active input Universal Input X2 The secondary input for a Siemens Ni 1000 temperature sensor a Pt 1000 temperature sensor an active passive remote setpoint transmitter or a 0 to 10 Vdc active input Digital Input D1 Selects the day night changeover Changeover occurs via potential free contacts between D1 and M Typically a time clock controls D1 input Analog Output Y1 Output Y1 can...

Page 6: ...auxiliary function in Night mode TH0756R1 X1 Y1 Q1 Temp Y X2 Q1 Figure 13 Remote Setpoint A remote setpoint transmitter QAA25U connected to X2 and configured accordingly enables setpoint adjustment Active measurement from 0 to 10 Vdc corresponding adjustable range from 100 to 8000 units Passive measurement from 0 to 1000 Ω corresponding adjustable range from 100 to 8000 units Cascade Control TH075...

Page 7: ...hangeover Summer operation is selected when the contact is closed Reverse acting output Y1 only is set to direct action cooling Analog changeover Summer operation is selected when the X2 input exceeds the Setpoint Reverse acting output Y1 only is set to direct action cooling NOTE The reverse acting output changeover occurs in Y1 only for application numbers 36 37 56 and 57 and in Q1 only for 16 17...

Page 8: ...tons on the controller front Additional tools are not necessary The controller can also be programmed via the software tool which plugs into the nine pin port TH0762R1 LCD Display Software Tool Nine Pin Port Program and Display Function Buttons Figure 19 RWD68U Universal Controller LCD The LCD shows the following information for normal operation Current operating values maximum four digits Current...

Page 9: ...nsformers with double insulation they must be designed for 100 duty When using several transformers in one system the connection terminals G0 ground must be galvanically connected Supplying voltages above 24 Vac to low voltage connections may damage or destroy the controller or any other connected devices Connections to voltages exceeding 24 Vac endanger personal safety The ARG62 21 Protective Hou...

Page 10: ... PC 9 pin plug TH0764R1 Y1 G Y1 S1 D1 GO Y B M B M X1 X2 M M X2 X1 M M GO G 24 V SN 24 V SP N1 TOOL PC Q12 Q14 Q11 Q1 E1 G G E1 Electrical load N1 RWD68U Controller PC Personal computer Q1 Potential free relay contacts for two position control S1 Time clock or switch SN System neutral SP System potential X1 Main input Termination G appears when X1 is an active sensor X2 Auxiliary input or remote s...

Page 11: ...tive owners 2005 Siemens Building Technologies Inc Siemens Building Technologies Inc 1000 Deerfield Parkway Your feedback is important to us If you have comments about this document please send Dimensions In Inches Millimeters TH0765R1 5 12 130 4 17 106 3 50 89 1 80 45 7 4 37 111 2 22 56 5 1 89 47 9 1 22 31 0 16 4 0 16 4 Figure 23 RWD68U Controller Dimensions TH0745R1 5 91 150 7 87 200 2 41 61 2 F...