Function Summary 

• 

Controller 
Stand-alone controller with one direct or reverse acting 0 to 10 Vdc output and 
one two-position (ON/OFF) output with dependent and independent adjustment 
on each sequence for direct acting or reverse acting. Adjustable parameters, 
including proportional band and integral action time. 

• 

Auxiliary selectable function 

• 

Universal input X2 for one of the following auxiliary functions: 

− 

P+I limiter function (Absolute and Relative) 

− 

Remote setpoint 

− 

Cascade control 

− 

Setpoint compensation 

− 

Winter/summer operation 

− 

Maximum priority 

• 

Digital input D1 for setpoint changeover day/night

 

Equipment 
Combinations 

The following Siemens devices can be connected to RWD68U Universal Controllers. 
Other combinations with units from third-party manufacturers are possible, if the 
input and output specifications match the RWD68U. 

 Table 

1.

 

Description Document 

Number 

Sensor with Siemens Ni 1000 temperature sensing element 
QAA25U Room temperature sensor with setpoint adjuster 

155-330 

Differential Pressure Sensor 

155-719 

GIB Series 310 lb-in Non Spring Return Actuators 
GBB Series 177 lb-in Non Spring Return Actuators 

155-176P25 
155-177P25 

GEB Series 132 in-lb Non Spring Return Actuators 

155-318P25 

GCA Series 142 in-lb Spring Return Actuators 

155-173P25 
155-174P25 
155-175P25 

GMA Series 62 in-lb Spring Return Actuators 

155-315P25 

SKD Valve Actuator with proportional input 
SKD Valve Actuator with floating input 

155-180P25 
155-181P25 

SKB/SKC Valve Actuator with proportional input 
SKB/SKC Valve Actuator with floating input 

155-163P25 
155-171P25 

SQX Valve Actuator with proportional input 
SQX Valve Actuator with floating input 

155-182P25 
155-186P25 

SQS Actuator with proportional input 
SQS Actuator with floating input 

155-190P25 
155-191P25 

SSC Actuator with proportional input 
SSC Actuator with floating input 

155-313P25 
155-314P25 

SSB Actuator with proportional input 
SSB Actuator with floating input 

155-192P25 
155-195P25 

SFA/SFP two-position valve actuators 

155-321P25 

Electric Rack and Pinion two-position actuator 

155-541P25 

1/2 to 2-inch two-way globe valves 

155-184P25 

1/2 to 2-inch three-way globe valves 

155-185P25 

2-12 to 6-inch two-way flange valves 

155-159P25 

2-1/2 to 6-inch three-way flange valves 

155-160P25 

MT Series 1/2 to 1-1/2-inch two-way globe valves 

155-196P25 

MT Series 1/2 to 1-1/2-inch three-way globe valves 

155-197P25 

MZ Series 1/2 to 1-inch two-way globe valves 

155-198P25 

MZ Series 1/2 to 1-inch three-way globe valves 

155-199P25 

1/2 to 1-inch zone valves 

155-320P25 

Siemens Building Technologies, Inc. 

Page 3

 

Summary of Contents for RWD68U

Page 1: ...gies program software NOTE For complete supporting technical documentation including training presentations see www us sbt siemens com hvp components Features Stand alone electronic temperature controller with P or P I response 24 Vac operating voltage Control application selectable via Application Number Active input scale can be selectable Limit and direction of the output scale can be freely as...

Page 2: ... to 916 Energy Management Equipment Terminals Screw terminals min max conductors Minimum 24 AWG 1 Maximum 16 AWG 2 or 14 AWG 1 Weight RWD68U Controller 10 72 oz 304 grams With packaging 12 64 oz 358 grams Analog Inputs X1 X2 Siemens Ni 1000 ohm 32 F 0 C Controller measuring range 58 F to 302 F 50 C to 150 C Maximum cable length for 14 AWG 984 ft 300 m Pt 1000 ohm at 32 F 0 C Controller measuring r...

Page 3: ...5 155 177P25 GEB Series 132 in lb Non Spring Return Actuators 155 318P25 GCA Series 142 in lb Spring Return Actuators 155 173P25 155 174P25 155 175P25 GMA Series 62 in lb Spring Return Actuators 155 315P25 SKD Valve Actuator with proportional input SKD Valve Actuator with floating input 155 180P25 155 181P25 SKB SKC Valve Actuator with proportional input SKB SKC Valve Actuator with floating input ...

Page 4: ...se acting independent and dependent control loop or Y2 and Q1 Direct and direct acting independent and dependent control loop NOTE Direct Acting As air temperature increases the control output increases Reverse Acting As air temperature increases the control output decreases TH0599R3 TEMPERATURE SENSOR AIR DAMPER ACTUATOR HEATING COIL COOLING COIL HEATING OR COOLING COIL TWO PIPE FAN OR PUMP TIME ...

Page 5: ... or a 0 to 10 Vdc active input Universal Input X2 The secondary input for a Siemens Ni 1000 temperature sensor a Pt 1000 temperature sensor an active passive remote setpoint transmitter or a 0 to 10 Vdc active input Digital Input D1 Selects the day night changeover Changeover occurs via potential free contacts between D1 and M Typically a time clock controls D1 input Analog Output Y1 Output Y1 can...

Page 6: ...auxiliary function in Night mode TH0756R1 X1 Y1 Q1 Temp Y X2 Q1 Figure 13 Remote Setpoint A remote setpoint transmitter QAA25U connected to X2 and configured accordingly enables setpoint adjustment Active measurement from 0 to 10 Vdc corresponding adjustable range from 100 to 8000 units Passive measurement from 0 to 1000 Ω corresponding adjustable range from 100 to 8000 units Cascade Control TH075...

Page 7: ...hangeover Summer operation is selected when the contact is closed Reverse acting output Y1 only is set to direct action cooling Analog changeover Summer operation is selected when the X2 input exceeds the Setpoint Reverse acting output Y1 only is set to direct action cooling NOTE The reverse acting output changeover occurs in Y1 only for application numbers 36 37 56 and 57 and in Q1 only for 16 17...

Page 8: ...tons on the controller front Additional tools are not necessary The controller can also be programmed via the software tool which plugs into the nine pin port TH0762R1 LCD Display Software Tool Nine Pin Port Program and Display Function Buttons Figure 19 RWD68U Universal Controller LCD The LCD shows the following information for normal operation Current operating values maximum four digits Current...

Page 9: ...nsformers with double insulation they must be designed for 100 duty When using several transformers in one system the connection terminals G0 ground must be galvanically connected Supplying voltages above 24 Vac to low voltage connections may damage or destroy the controller or any other connected devices Connections to voltages exceeding 24 Vac endanger personal safety The ARG62 21 Protective Hou...

Page 10: ... PC 9 pin plug TH0764R1 Y1 G Y1 S1 D1 GO Y B M B M X1 X2 M M X2 X1 M M GO G 24 V SN 24 V SP N1 TOOL PC Q12 Q14 Q11 Q1 E1 G G E1 Electrical load N1 RWD68U Controller PC Personal computer Q1 Potential free relay contacts for two position control S1 Time clock or switch SN System neutral SP System potential X1 Main input Termination G appears when X1 is an active sensor X2 Auxiliary input or remote s...

Page 11: ...tive owners 2005 Siemens Building Technologies Inc Siemens Building Technologies Inc 1000 Deerfield Parkway Your feedback is important to us If you have comments about this document please send Dimensions In Inches Millimeters TH0765R1 5 12 130 4 17 106 3 50 89 1 80 45 7 4 37 111 2 22 56 5 1 89 47 9 1 22 31 0 16 4 0 16 4 Figure 23 RWD68U Controller Dimensions TH0745R1 5 91 150 7 87 200 2 41 61 2 F...

Reviews: