12.5 Electrical
data
Power supply (switching network section)
AC 110...240 V +10/-15%
48...63 Hz
Electrical safety
To DIN EN 60730, part 1
Overvoltage category II
Degree of contamination 2
Power consumption
Max. 16 VA
Data backup
EEPROM
Electrical connection
At the rear via screw terminals
- Cross-sectional area
0.25...1.5 mm² fine-wired
- Stranded wire with
- Ferrules to DIN 46228
- Pin-type cable socket to DIN 46231
- Crimp-type cable socket in fork-form for
M3 thread (dimensions to DIN 46237)
With UL applications
Use of the cable lug or ferrules to
UL486A-B (UL listed or recognized)
Tightening torque
0.5 Nm
Electromagnetic compatibility
DIN EN 61326-1
Emitted interference
Class B
Immunity
Meeting industrial requirements
12.6 Housing
Type of housing
Made of Makrolon for control panel
mounting to DIN IEC 61554
(use in indoor)
Color Light-grey
RAL7035
Mounting depth
92 mm
Mounting position
Optional
Degree of protection
To DIN EN 60529
Front side IP66
Rear IP20
Weight (Fully
equipped)
- RWF50.2
Approx. 170 g
- RWF50.3
Approx. 168 g
58/68
20089337