25/93
Building Technologies Division
User Manual RWF55...
CC1U7867en
Infrastructure & Cities Sector
5 Operating modes
05.11.2013
5.2.3 2-stage burner, 3-position output
In area (1), the thermostat function is active. In area (2), the RWF55 as a
2-position
controller
acts on the second stage via relay K2 (OPEN) and relay K3 (CLOSE) by
switching on at switch-on threshold
HYS1
and switching off at switch-off threshold
HYS2
.
7866d07/0911
Figure 10: Control sequence of 2-stage burner, 3-position output
In area (3), the actual value exceeds the upper switch-off threshold
HYS3
and the
controller shuts down the burner (
B
). The controller only starts low-fire operation when
the actual value falls again below switch-on threshold
HYS1
. If the response threshold
(q) is exceeded, the controller switches to high-fire operation (
A
).
Reference!
See chapter 5.6
Response threshold (q).