48/93
Building Technologies Division
User Manual RWF55...
CC1U7867en
Infrastructure & Cities Sector
7 Parameterization PArA
05.11.2013
78
67z
06
/061
2
Parameter Display
Value
range
Factory
setting
Remarks
Outside temperature
Curve point 1 ¹
At1
-40...120
-10
Reference!
See chapter 5.5
Weather-compensated
setpoint shifting
Boiler temperature
Curve point 1 ¹
Ht1
SPL
...
SPH
60
Reference!
See chapter 5.5
Weather-compensated
setpoint shifting
Outside temperature
Curve point 2 ¹
At2
-40...120
20
Reference!
See chapter 5.5
Weather-compensated
setpoint shifting
Boiler temperature
Curve point 2 ¹
Ht2
SPL
...
SPH
50
Reference!
See chapter 5.5
Weather-compensated
setpoint shifting
¹
Setting of decimal place has an impact on this parameter
Note!
When using the RWF55… as a modulating controller only, or as a modulating
controller without the burner release function (1P, 1N), parameter
HYS1
must be set to
0
and parameters
HYS2
and
HYS3
must be set to their
maximum
values.
Otherwise, for example, when using default parameter
HYS1
(factory setting -5), the 3-
position controller is only released when the control deviation reaches -5 K.