61/93
Building Technologies Division
User Manual RWF55...
CC1U7867en
Infrastructure & Cities Sector
8 Configuration ConF
05.11.2013
8.10 Interface
IntF
The controller can be integrated into a data network using an optional RS-485 interface
or an optional Profibus DP interface.
ConF
IntF
Parameter Value/
selection
Description
Baud rate
bdrt
Baud rate
0 4800
Baud
1 9600
Baud
2 19200
Baud
3 38400
Baud
Device address
Modbus
Adr
Device address
0...
1
...
254
Address in the data network
Device address
Profibus
dP
Device address
0...
125
Only RWF55.6
Remote Detection
Timer
dtt
Remote detection timer
0...
0 = Switched-off
30
...
7200 s
Note!
If communication is taking place via the setup interface, the other interfaces are
inactive.