Building Technologies

Fire Safety & Security Products

 

SAP14 

External power supply 

Installation instructions 

 

 

Product description 

The SAP14 is a power supply unit suitable for an E-Bus 
and has an output voltage of 12 V at a maximum of 1.3 
A. The housing offers space for four type SMT12 (trans-
ponder) and for a battery of up to 12 V, 17 Ah for VdS 
applications or up to 12 V, 17 Ah for non-VdS 
applications. At least one SMT12 must be fitted to use 
the cover tamper contact. 

 

 

Security 

z

 

Keep this document for later reference. 

z

 

Also follow the country-specific safety standards or 
regulations for project planning, operating and dispo-
sing of the product. 

z

 

The device is always to be disconnected from the 
mains or battery prior to performing maintenance work 
or installing additional devices. 

Liability claim 

z

 

Do not connect the device if components are missing 
or damaged. 

z

 

Only make changes to the unit that are explicitly 
mentioned in this document or which have been 
approved by the manufacturer.  

z

 

Use only spare parts and accessories approved by the 
manufacturer. 

Damages due to a inappropriate mounting location 

z

 

Observe the environmental requirements recom-
mended by the manufacturer.  

z

 

Do not operate the unit in areas exposed to extreme 
dust formation, moisture, vibration or flammable 
gases. 

 

Summary of Contents for SAP14

Page 1: ...pecific safety standards or regulations for project planning operating and dispo sing of the product z The device is always to be disconnected from the mains or battery prior to performing maintenance work or installing additional devices Liability claim z Do not connect the device if components are missing or damaged z Only make changes to the unit that are explicitly mentioned in this document o...

Page 2: ...lities Danger of explosion z Make sure that the battery poles do not short circuit z Please pay attention to battery polarity z Always fasten the battery in place with the holder intended for this purpose Technical data Mains voltage 230 V AC 10 15 50 Hz Power intake max 34 VA at 230 V AC Mains supply fuse 160 mA T Mains power Output voltage current 13 7 V DC 1 3 A Max ripple at 1 3 A 60 mV Relay ...

Page 3: ... 3 Fig 1 2 Remove cover 1 2 4 5 6 7 10 3 8 9 R45 F1 B4 F2 1 F3 3 F4 4 F5 6 Fig 2 Power supply assembly circuit board SMP14 1 LED flashes when E bus communication is intact 2 Address button 3 Not used 4 E Bus connection to burglary detection control unit B1 B2 B3 B4 B4 is secured by F1 5 4 outputs 12 V 1 3 4 6 which are each secured with a fuse F2 to F5 6 Output for mains supply indication not fuse...

Page 4: ...y 1 5 cm proud B Fig 3 4 Snap the spacers in at the four mounting holes from the back in the intended slots Fig 3 5 Route the connection cable through the cut outs D in the back wall and hang the back on the screws 6 Tighten the screws Fig 4 Mount boards option 1 Snap the fastening supports included with the board into the intended holes A Fig 4 2 Fit circuit boards B Fig 4 Wiring The terminals ca...

Page 5: ...he base of the housing 4 Connect the mains to the mains supply terminals ground wire E null N and phase U 5 Secure the cable to the clips in the rear wall using cable ties Fig 6 A E bus from control unit B E Bus to other accessories E Bus Cable type IYSTY 2 x 2 x Ø 0 6 mm is recommended The total length of the E Bus cable must not exceed 500 m The power supply unit circuit board SMP14 and the opti...

Page 6: ...battery in the space provided in the base of the housing 2 Mount the battery holder angle 3 Connect the pre installed battery cables blue red Fig 9 Close and seal the housing 1 Glue the circuit diagram to the inside of the cover 2 Engage the cover in the retainer 3 Connect the earthing lead 1 Fig 9 to the cover 4 Lightly lift and close the cover 5 Screw the cover closed 6 Use eye 2 Fig 9 to seal W...

Page 7: ...duct indicates that the product is subject to EU Directive 2002 96 EC Proper disposal and separate collection of such equipment is intended to prevent potential harm to health and the environment They are prerequisites for re use and recycling of used electrical and electronic devices Detailed information on the disposal of used equipment can be obtained from your local authorities your waste disp...

Page 8: ...mbH Co oHG 76181 Karlsruhe Germany www buildingtechnologies siemens com 2009 Copyright by Siemens Building Technologies Liefermöglichkeiten und technische Änderungen vorbehalten Data and design subject to change without notice Document no A6V10236281 Edition 19 01 2009 ...

Reviews: