4. Wiring

The terminals are shown in fig. 3 and on the wiring 
diagram glued to the inside of the cover.

4.1 E-Bus (fi g. 6)

Cable type 24 AWG 7 x Ø 0,2 mm is recommended.  
The to tal length of the E-Bus cable must not exceed 
500 m. The E-Bus must be connected to the cen tral 
control unit (B1-, B2, B3, B4+).  It may be routed in 
parallel to other accessories.  If shielded cable is used, 
all the shields must be connected at one point, e.g. at 
an NC terminal.

4.2 Tamper  contact

If the SMT 12 circuit board is not fitted in the SAT 
12 housing, the plug connector (fig. 3 

W

) must be 

connected to an external tamper contact or be short-
circuited. Use the socket connector provided to connect 
to an external tamper con tact.

4.3 Inputs (fi g. 7)

All inputs can be operated in modes 1 to 4 and 6 to 
7 (fig. 7). Inputs Z1 to Z2 can also be operated with 
glass break alarms. To do this, the relevant switches 
SW1 to SW2 must be closed and one terminal of each 
glass break sensor connected to one of outputs O1 to 
O2, which must be programmed for «Latching sensor 
reset». When wiring fire detectors, any trou ble out put 
present can be looped directly into the line.  For fire 
detectors where the power has to be disconnected 
to reset the alarm, the negative can be connected 
via an output which is programmed as a «Latching 
sensor reset» output.
The emergency exit has to be wired like mode 6. A 
short circuit of the input will reset the corresponding 
output.

5. Close and seal the housing

1  -  Engage the cover in the retainer at the top (fig. 1).
2 -  Close the cover and tighten the retaining screw
       (fig. 1).
3 -  Use eye (fig. 2 

R

) for sealing.

6. Technical  data

Supply 

from the E-Bus 

Power consumption min.  

6 mA

Power consumption max. 

19 mA 

2 outputs «open collector» 

12 V, 150 mA 

4 inputs 

Programmable

Terminating resistors  

4.7 kOhm 

Operating temperature  

-10° C to +55° C 

Housing  

ABS 

Dimensions in mm, SAT 12           H 86 x W 135 x D 
27   Safety class, SAT 12  

IP 30 

Environmental class, SAT 12 

II

Weight, SAT 12  

130 g

Dimensions in mm, SMT 12        H 52 x W 91 x D 20
Weight, SMT 12 

50 g

E-Bus from the 
central control unit

E-Bus to other 

accessories 

B4+

B3

B2

B1-

5. Glass break sensors

Z

O

4k7

Z1
Z2

SW 1
SW 2

4k7

4k7

Z

Tamper

Alarm

Input modes

1. Normally open contact

2. Normally closed contact

4. Alarm & tamper monitored

6. Emergency exit

7. Fire input

4k7

4k7

Z

Tamper

Reset

Alarm

Z

4k7

Alarm

Trouble

Closed

Input

Open

Switch

To connect a maximum
of 20 glass break sensors

All other modes

4k7

Z

Z

Z

3. Normally closed contact

monitored