Internal Accessories
Preliminary Installation Proced ures
A
DANGER
H azardous Voltage.
Will cause severe inju ry or death.
If practical turn power off an d lock out
su pplying device before man ipu latin g the
M oveable Draw ou t E lemen t.
A
WARNING
Mechan ism can cause severe
inju ry when cover is removed.
Bef ore removing cover, push open
button, push close button, push open
button again.
CAUTION: All internal accessories should be installed
with the circuit breaker removed from service. If ac
cessories are to be installed while circuit breaker is
in service, turn off and lockout power supplying the
circuit breaker prior to cover removal and accessory
installation.
NOTE: The accessory installation procedures out
lined in this booklet are general by nature and may not
contain the latest up to date information for com
plete installation. Therefore it is Siemens' recommen
dation that all accessories be installed utilizing the
instruction information accompanying the accessory.
1 .)
Prior to cover removal check to be sure the circuit breaker
main contacts are open and the closing springs are dis
charged by first pushing the open button.
2.) Push the close button and then repeat pushing of the
open button.