External Accessories
U niversal Test Kit (TS-3 1 )
Enter one of the following letters:
"A"-Phase A or Left Pole
"B"-Phase B or Center Pole
"C"-Phase C or Right Pole
H.
The TS-3 1 will report the type of test you selected and
give you a chance to abort the test. For example, if
"I"
was pressed above. The TS-31 will display:
Instantaneous Test
Press ENTER to Continue or A to Abort.
If you pressed the letter "A" to abort, you will be asked
to enter again.
Change:
1
- Test 2 - Catalog 3 - Settings:
I . Press Enter again to start the test. Press any other key
to STOP the test. Once a test has been started , the
TS-31 will respond with :
Trip test. Press Any Key to Abort.
Time Remaining: xx.xxx Sec.
Be careful at this time. Any key press will abort the test.
J.
The test may take anywhere from a fraction of a sec
ond to minutes to complete, depending on which proce
dure was run. If the test passes, the display will show
the following, depending on whether the breaker tripped
or not.
Test Passed . xxx.xx seconds
Press any key to continue.
If the breaker tripped during the test, RESET the circuit
breaker before continuing.
K. The TS-31 will prompt for the next instructions. The
d isplay will show:
Change: 1 - Test 2 - Catalog 3 - Settings
Enter one of the following numbers:
" 1 "
- select a new test
"2" - enter a new catalog number
"3" - enter a new switch setting
If you enter " 1 " you wil l be sent to step F. Choosing a "2"
will send the program back to step E. Entering "3" which
sends you back to step E, will be slightly different the
second time through. On the second line after the
prompt for the setting, a number or text in brackets will
appear. This will indicate the last setting you entered. If
you DON'T wish to change a setting , just press ENTER.
If you DO wish to change a setting, type in the new
setting and press ENTER.
L.
If you pressed "C" when asked.
You will first be prompted by:
Current Transformer Test
Press ENTER to Continue or A to abort.
and then for the phase to test. A message will then
appear stating the test results. For example:
CT Resistance Test. Phase X PASSED.
Press any key to continue.
M . There are additional ERROR messages which may
appear on the d isplay during this operation which
were not covered previously
Test Not Running - Check Test Cable.
Press enter to continue.
The test set has sensed that current is not flowing
properly in the breaker under test and that there is either
an open or short circuit between the TS-31 and the
breaker trip unit.
Ground Fault is NOT available on a SJD69300.
Press any key to continue.
You will get this error message if you enter a choice
that is not available, such as entering "G" in step F for
ground fault test on a catalog number that does have
g round fault.
I nconclusive Test, Check Settings.
Press any key to continue or A to abort.
Note:
This warning will appear if you attempt to run a
short time test with the instantaneous pickup set
equal to or below the short time pickup. It would
also appear if you tried to run a long time test
with short time pickup set to 2. This is only a
warning: the test can still be run. However, passing
or failing the test may not be conclusive.
XX is NOT a Valid Setting.
Press any key to continue.
Note:
This message will appear if you enter a setting
val u e that does not exist. For exam p l e a
SMD69700ANGT has continuous current settings
of 20, 30, 40, 50, 60, 70, 80, 90, 1 00 percent. If you
were to enter any other value than those listed,
the above message will appear.
Test Exceeds Capability of TS-31 .
Press any key to continue.
Note:
This message is not likely to occur. If it does, it
means that a test requires more current to run than
the TS-31 can produce.
Unit Too Hot, Please Wait.
Note:
Running many successive high-current long
time tests may over-heat the test set. It will protect
itself from damage by preventing further tests
until it has had a chance to cool down . The display
will indicate when testing can resume.