Internal Accessories
49
5.) Install the latch check switch assembly (see Figure 2).
Secure the latch check switch assembly to the mecha-
nism plate using (2) #6 screws provided. Do not tighten
screws until the latch check switch assembly is properly
adjusted.
6.) Adjust switch (see Figure 3). When switch is properly
adjusted tighten screws. Note: Torque screws to 8-11
in. Ibs.
7.) After tightening screws check to ensure that tightening
of screws did not affect switch adjustment.
8.) Locate the reset mechanism (See Figure 5).
9.) To mount the “B” switch, first make sure that the switch
lever is inside the top cavity of the pusher link (See Figure
4).
10.) Make sure that the switch lever rests on the pusher link
when the breaker main contacts are open (See Figure 4).
Place insulator between “B” switch and bracket. Secure
that “B” Switch with the (2) #4 screws provided. Note:
Torque screws to 5-6 in. Ibs.
11.) Route wires from “B” switch (See Figure 5). Route wires
beneath mechanism plates as shown. Install cable tie
mounts and cable ties (See Figure 5).
12.) Connect wire marked RC from “B” switch to solenoid
connector. (See Figures 4 and 5). Connect wires marked
LC-B together.
Remote Close Assembly
Figure 2. Latch Check Switch Adjustment
Figure 3. Latch Check Switch Assembly
Figure 4. “B” Switch Mounting
Summary of Contents for SBA 1200
Page 68: ...66 External Accessories Ground Fault Sensing and Relaying Courtesy of NationalSwitchgear com ...
Page 94: ...92 Outline Dimension Drawing 2000A Fixed Mounted Courtesy of NationalSwitchgear com ...
Page 95: ...93 Outline Dimension Drawing 2000A Fixed Mounted Courtesy of NationalSwitchgear com ...
Page 100: ...98 Courtesy of NationalSwitchgear com ...
Page 101: ...Electrical Diagrams 99 Courtesy of NationalSwitchgear com ...
Page 102: ...100 Electrical Diagrams Courtesy of NationalSwitchgear com ...