Internal Accessories
51
Remote Close Assembly
Remote Close Schematic
16. Replace the breaker cover. Check to ensure that wires
exit the breaker through the wire guide and are not
pinched by the breaker cover Torque #10 (corner) cover
screws to 28-32 in.-lbs. Torque 1/4' cover screws to 68-
75 in.-lbs.
17 For fixed mounted breakers connect the insulated termi-
nals to the proper terminal block locations. For drawout
breakers follow steps 18 and 19
18. Route wires through the hole in the drawout movable
element. (Figures 7).
19. Connect the insulated terminals to the proper secondary
disconnect locations (See Figure 7).
Figure 7.